IB505040EN 049-286Installation Instructions for the Sure-Lites UX6 AC only Exit Sign. UX6 Exit Signsand Markers for Use in HAZARDOUS LOCATIONSWARNINGRisk of Fire/Electric ShockIf not qualified, consult an electrician.WARNINGRisk of Electric ShockDisconnect power at fuse or circuit breaker beforeinstalling or servicing.Important SafeguardsWHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETYPRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDINGTHE FOLLOWING.1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS2. Do not use near gas or electric heaters.3. Do not use this equipment for other than the intended use.4. Installation is to be performed only by qualified personnel.5. Install in accordance with National Electric Code and localregulatory agency requirements.6. The use of accessory equipment not recommended by themanufacturer may cause an unsafe condition.7. Equipment should be mounted in locations and at heightswhere it will not readily be subjected to tampering byunauthorized personnel.8. SAVE THESE INSTRUCTIONSSure-LitesINSTALLATION – HAZARDOUS LOCATIONSNOTE: Wall or ceiling mounting using the canopy kit is notintended for hazardous locations. The canopy kit is notsuitable for Hazardous Locations and is meant Non-Hazardous Locations installation only.NOTE: For hazardous location compliance, the UX must beinstalled using the provided conduit hub. The UX shouldnot be directly mounted to a junction box when used inhazardous locations.1. For field supply connection to the unit, use suitable wiringmethod for the hazardous location per NEC. Circuit shouldnot be energized at this time.2. Remove the weather shield by removing the 4 screws inthe corners (See Figure 1). Due to the airtight nature of theexit sign, the weather shield may be held on by a slightvacuum. If this occurs, carefully pry the corners of theshield with a flat head screwdriver, but do no damage thewater shield or inner gasket.3. Remove the stencil face by prying the snap fits on the sideup, by placing a flat head screw driver in the slots andlifting (See Figure 1).4. Choose the appropriate knock out for the mounting (leftside, right side, or top or backplate), and knock it out usinga hammer and flat blade screwdriver. Connect conduitusing the ½” fitting provided (See Figure 4).5. For single face units only, if needed, knock out the tworound knock outs at the far left and right of the backplate,and apply foam gasket to the back of the exit sign. Usethese holes to attach the UX to the wall using a standard#8 screw or larger. Only remove the gasket holes neededfor installation. For double face units, proceed to Step 6.NOTE: When mounting the UX, it is necessary to consider theweight of the exit sign, about 7 pounds. A suitable anchoris recommended, or mounting directly to a stud for thejunction box the exit sign is mounted to.6. After the frame is securely mounted, the stencil can behung for “hands free” wiring using the Sure-Lites EZ Hangsystem. (See figure 2).