AC platform power consumption (high-line input)The actual amount of power draw from the AC source depends on the type and number of blades and the power supplyAC source voltage and redundancy configuration. This table shows several possible configurations for high-line voltageand the typical and maximum power draw.Table 3: AC mains total system power draw (high-line input)Number of power suppliesinstalledMaximum system powerdrawTypical system power drawBlade quantity and type2900W675W1 x PB10021275W975W2 x PB10041650W1325W3 x PB10042025W1625W4 x PB1002925W700W1 x PB20021325W1025W2 x PB20041725W1400W3 x PB20042125W1725W4 x PB200DC power requirementsWhen working with a DC-powered VIPRION platform, it is important to understand the DC power options andrequirements.DC power redundancy provisioningThe platform supports one to four DC power supplies. Each slot is provisioned to draw up to 600W; therefore, one powersupply can support two blade slots with no redundancy. This table shows some of the possible blade and power supplyredundancy configurations.Table 4: DC power provisioning recommendations1 + 1 redundancyNo redundancyBlade quantity2 (1200W available)1 (1200W available)1 (600W)2 (1200W available)1 (1200W available)2 (1200W)4 (4800W available)2 (2400W available)3 (1800W)4 (4800W available)2 (2400W available)4 (2400W)56 | Platform Guide: VIPRION | Platform Specifications