1. The installer SHALL check available power to make certainit matches the unit (Name Plate Rating) and that constantvoltage can be maintained to the unit. Unsatisfactoryperformance would otherwise result. The local powercompany should be contacted on any problems or questionsconcerning power supply.2. Install a line service disconnect switch within sight of thecondensing unit. The line voltage service wiring for thecondensing unit should include a fused disconnect switch.3. Use correct wire size and fuse size. To ensure that adequatevoltage will be available at the condensing unit, the linevoltage service wiring MUST be of adequate size. Minimumrecommended wire ampacities and maximum fuse sizes arelisted on the unit name plate.4. Two holes are provided in the control box.a. One is for the connection of the line voltage conduitor cable. The hole is sized for 3 / 4 " conduit.b. One is for low-voltage wiring. (Refer to the wiringdiagram attached to electrical box cover forconnection.)5. Be sure to ground the condensing unit by securing theground wire to the grounding lug inside the control box.6. Be sure to follow National Electrical Code and all localcodes.ELECTRICAL HOOK-UPWARNING: ELECTRICAL EQUIPMENT SHOULD BEINSTALLED BY A QUALIFIED, LICENSED ELECTRICIAN.IMPROPER ELECTRICAL HOOK-UP MAY DAMAGEEQUIPMENT, CAN CREATE A HAZARD, CAUSE PERSONALINJURY OR DEATH, AND WILL VOID THE WARRANTY.!5When replacing an existing system, it is mandatory that a liquid line filter dryer (if not provided with the condensing unit) and a suction linefilter, conforming to the dryer selection chart below, be installed in the new system if any of the original refrigerant-bearing components areto be used in the new installation. This is to assure that any contaminants left in the original components will not harm the new system. Ifany other evaporator coils other than those manufactured or approved by our company are used in the installation, THE CLAIMEDPERFORMANCE AND WARRANTY WILL BE VOID without written notification and approval of such coils by our company.DRYER SELECTION CHART(Alco, Parker Hanifin, Sporlan)TONNAGE LIQUID LINE ALCO SUCTION LINE FILTER SPORLANFILTER DRYER PARKER HANIFIN2 053 35S5 SLD 8-5SV C-1652.5 053 35S5 SLD 8-5SV C-3053 083 45S6 SLD 13-6SV C-3063.5 163 45S6 SLD 13-6SV C-3064 163 45S6 SLD 13-6SV C-3075 165 45S7 SLD 13-7SV C-307Selection of dryers smaller than recommended will cause unsatisfactory pollution protection, excessive refrigerant charge and pressure drop.High pressure drops will result in reduced system capacities, higher system operating cost and increased failure rate.SPECIAL INSTRUCTIONS FOR REPLACEMENT APPLICATION