GE Multilin D60 Line Distance Relay 5-1835 SETTINGS 5.6 CONTROL ELEMENTS55.6.9 MONITORING ELEMENTSa) MAIN MENUPATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTSb) BREAKER ARCING CURRENTPATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS Ö BREAKER 1(4) ARCING CURRENT MONITORING ELEMENTS BREAKER 1 ARCING CURRENT See below.MESSAGE BREAKER 2 ARCING CURRENT See below.MESSAGE BREAKER FLASHOVER 1 See page 5–185.MESSAGE BREAKER FLASHOVER 2 See page 5–185.MESSAGE VT FUSE FAILURE 1 See page 5–189.MESSAGE VT FUSE FAILURE 2 See page 5–189.MESSAGE VT FUSE FAILURE 3 See page 5–189.MESSAGE VT FUSE FAILURE 4 See page 5–189.MESSAGE OPEN POLE See page 5–190. BREAKER 1 ARCING CURRENTBKR 1 ARC AMPFUNCTION: DisabledRange: Disabled, EnabledMESSAGE BKR 1 ARC AMPSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4MESSAGE BKR 1 ARC AMP INT-A:OffRange: FlexLogic™ operandMESSAGE BKR 1 ARC AMP INT-B:OffRange: FlexLogic™ operandMESSAGE BKR 1 ARC AMP INT-C:OffRange: FlexLogic™ operandMESSAGE BKR 1 ARC AMPDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BKR 1 ARC AMP LIMIT:1000 kA2-cycRange: 0 to 50000 kA 2-cycle in steps of 1MESSAGE BKR 1 ARC AMP BLOCK:OffRange: FlexLogic™ operandMESSAGE BKR 1 ARC AMPTARGET: Self-resetRange: Self-reset, Latched, DisabledMESSAGE BKR 1 ARC AMPEVENTS: DisabledRange: Disabled, Enabled