GE Multilin D60 Line Distance Protection System B-23APPENDIX B B.4 MEMORY MAPPINGB42D6 ...Repeated for User-Programmable LED 4442D8 ...Repeated for User-Programmable LED 4542DA ...Repeated for User-Programmable LED 4642DC ...Repeated for User-Programmable LED 4742DE ...Repeated for User-Programmable LED 48Installation (Read/Write Setting)43E0 Relay Programmed State 0 to 1 --- 1 F133 0 (Not Programmed)43E1 Relay Name --- --- --- F202 “Relay-1”User Programmable Self Tests (Read/Write Setting)4441 User Programmable Detect Ring Break Function 0 to 1 --- 1 F102 1 (Enabled)4442 User Programmable Direct Device Off Function 0 to 1 --- 1 F102 1 (Enabled)4443 User Programmable Remote Device Off Function 0 to 1 --- 1 F102 1 (Enabled)4444 User Programmable Primary Ethernet Fail Function 0 to 1 --- 1 F102 0 (Disabled)4445 User Programmable Secondary Ethernet Fail Function 0 to 1 --- 1 F102 0 (Disabled)4446 User Programmable Battery Fail Function 0 to 1 --- 1 F102 1 (Enabled)4447 User Programmable SNTP Fail Function 0 to 1 --- 1 F102 1 (Enabled)4448 User Programmable IRIG-B Fail Function 0 to 1 --- 1 F102 1 (Enabled)4449 User Programmable Ethernet Switch Fail Function 0 to 1 --- 1 F102 0 (Disabled)CT Settings (Read/Write Setting) (6 modules)4480 Phase CT 1 Primary 1 to 65000 A 1 F001 14481 Phase CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)4482 Ground CT 1 Primary 1 to 65000 A 1 F001 14483 Ground CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)4484 ...Repeated for CT Bank 24488 ...Repeated for CT Bank 3448C ...Repeated for CT Bank 44490 ...Repeated for CT Bank 54494 ...Repeated for CT Bank 6VT Settings (Read/Write Setting) (3 modules)4500 Phase VT 1 Connection 0 to 1 --- 1 F100 0 (Wye)4501 Phase VT 1 Secondary 50 to 240 V 0.1 F001 6644502 Phase VT 1 Ratio 1 to 24000 :1 1 F060 14504 Auxiliary VT 1 Connection 0 to 6 --- 1 F166 1 (Vag)4505 Auxiliary VT 1 Secondary 50 to 240 V 0.1 F001 6644506 Auxiliary VT 1 Ratio 1 to 24000 :1 1 F060 14508 ...Repeated for VT Bank 24510 ...Repeated for VT Bank 3Source Settings (Read/Write Setting) (6 modules)4580 Source 1 Name --- --- --- F206 “SRC 1"4583 Source 1 Phase CT 0 to 63 --- 1 F400 04584 Source 1 Ground CT 0 to 63 --- 1 F400 04585 Source 1 Phase VT 0 to 63 --- 1 F400 04586 Source 1 Auxiliary VT 0 to 63 --- 1 F400 04587 ...Repeated for Source 2458E ...Repeated for Source 34595 ...Repeated for Source 4459C ...Repeated for Source 545A3 ...Repeated for Source 6Power System (Read/Write Setting)4600 Nominal Frequency 25 to 60 Hz 1 F001 604601 Phase Rotation 0 to 1 --- 1 F106 0 (ABC)4602 Frequency And Phase Reference 0 to 5 --- 1 F167 0 (SRC 1)4603 Frequency Tracking Function 0 to 1 --- 1 F102 1 (Enabled)Table B–9: MODBUS MEMORY MAP (Sheet 15 of 60)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT