Chapter 2. CPU Features & SpecificationsGFK-2222AD April 2018 212.1.6 Embedded PROFINET ControllerThe following CPUs support a feature that permits an Ethernet LAN to be configured for use as aPROFINET Controller:• RX3i CPE40011• Rx3i CPE33012• RSTi-EP CPE100/CPE11513If the Embedded PROFINET Controller feature is to be configured, it must be configured on LAN2 for theCPUs listed above. In the case of RX3i CPE400 and RSTi-EP CPE100/CPE115, which are Standalone CPU’s,this will be its only PROFINET Controller. In the case of CPE330, the Embedded PROFINET Controller canco-exist with any rack-mounted PROFINET Controllers (IC695PNC001) present in its CPU rack.To enable the Embedded PROFINET Controller in a project in Proficy Machine Edition14, select the RX3iCPE400 (or CPE330) or RSTi-EP CPE100/CPE115 target in the PME Navigator (Figure 1) and open theHardware Configuration. On the Settings tab, change the designated LAN Mode of the selected port toPROFINET. The PROFINET Controller node description then displays that a PROFINET node exists on theselected LAN.For further details, refer to the PACSystems RX3i & RSTi-EP PROFINET IO-Controller User Manual,GFK-2571G or later.Figure 1: Configuring an Embedded PROFINET ControllerA PROFINET configuration may be transferred between a PROFINET Controller module (IC695PNC001)and the target Embedded PROFINET IO-Controller using the cut / copy / paste or equivalent drag anddrop functions in Proficy Machine Edition.Note: If the PME Project has PROFINET redundant devices, you must record any unique SecondaryTarget information and disable Redundancy before cut / copy / paste functions on PROFINETController modules will work. Then, re-enable Redundancy, mirror, and restore your uniqueSecondary Target information.11 CPE400 firmware version 9.00 or later is required for the embedded PROFINET Controller feature.12 CPE330 firmware version 8.90 or later is required for the embedded PROFINET Controller feature.13 Proficy Machine Edition™ (PME) 9.50 SIM 4 or later is required in order to configure the MRP parameters for CPE100/CPE115.14 Proficy Machine Edition Logic Developer PLC 8.60 SIM 13 or 9.00 SIM 4 or later is required for configuration of the EmbeddedPROFINET Controller function.