Critical PowerModifications reserved Page 42/92GE_UPS_USM_TLE_SUL_M62_1M0_2US_V010.docx User Manual TLE Series 625 - 750 - 1000 UL S2Code Message Description4303 INVERTER CANNOT BE TURNED OFFInverter cannot be switched OFF, because theLoad cannot be switched to Utility (voltage out oftolerance, not synchronized, BP blocked).4361 INVERTER ON The command to start the Inverter has beenactivated on the control panel.4362 INVERTER OFFThe command to switch OFF the Inverter hasbeen activated by the control panel orautomatically for alarm presence.4411 BYPASS UTILITY OK Bypass Input Utility is again within tolerance(voltage, frequency and phase).4500 COMMAND LOAD OFF Disconnection of the Load by opening K6 and K7for: EPO / Load Off / Overload / Stop Operation.4521 NO BYPASS POWER With the Load supplied by Automatic Bypass, aUtility Failure or K6 opening occurred.4534 MULTIPLE LOAD TRANSFER 2 transfers Inverter- Utility have been detected ina short time (default 30 sec.).4535 BYPASS LOCKED Bypass is not available.Contactor K6 is open, SSM deactivated.4536 BYPASS FREE Bypass is enabled.Contactor K6 is closed.4561 LOAD OFFPush-button “Load Off” on the UPS Control Panelhas been pressed, with the output circuit switchQ1 closed.4562 DETOUR ONThe auxiliary contact indicates that ManualBypass Q2 (only if provided by customer) wasclosed.4564 DETOUR OFFThe auxiliary contact indicates that ManualBypass Q2 (only if provided by customer) wasopened.4567 COMMAND LOAD ON UTILITY The control unit received a command to transferthe Load on Utility.4568 COMMAND LOAD ON INVERTER The control unit received a command to transferthe Load on Inverter.4572 NO MORE OVERLOAD End of the overload condition detected withalarm 4570.4580 INVERTER AND UTILITY SYNCHRONIZED The voltages of Inverter and Utility Bypass aresynchronized.4582 COMMAND NOT TO SYNCHRONIZE Command not to synchronize with Utility.4583 COMMAND TO SYNCHRONIZE Command to synchronize with Utility.4600 COMMAND UPS ONThe eBoost operation mode function has beendisabled or the programmed time is expired.The UPS returns to VFI mode supplying the Loadnormally by Inverter.4601 COMMAND UPS STAND BYThe function eBoost operation mode is enabled,and according to the time program the UPS willrun in eBoost mode, supplying the Load normallyby utility.4602 Q1 OPEN The auxiliary contact indicates that the outputswitch Q1 was opened.4603 Q1 CLOSED The auxiliary contact indicates that the outputswitch Q1 was closed.