Critical PowerModifications reserved Page 7/43GE_UPS_ISG_LPS_3UL_20K_30K_2US_V010.docx Installation Guide LP33 Series 20 & 30 UL S2IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manual contains important instructions for UPS LP33 Series 20 & 30 that should befollowed during installation and maintenance of the UPS and battery.GENERAL- Move the UPS in an upright position in its original package to the final destination room.To lift the cabinets, use a forklift or lifting belts with spreader bars.- Check for sufficient floor and elevator loading capacity.- Check the integrity of the UPS equipment carefully.If you notice visible damage, do not install or start the UPS.Contact the nearest Service Center immediately.- WARNING! RISK OF ELECTRICAL SHOCK:Do not remove covers, there are no user serviceable parts inside.- After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltageremains at the terminals of the electrolytic capacitors.- UPS’s and battery system require a 12 months periodic maintenance to operate reliably and safely.This should be performed by qualified service personnel.The UPS contains its own energy source (battery).- The field-wiring outlets may be electrically live, even when the UPS is disconnected from the utility.- Dangerous voltages may be present during battery operation.- The battery must be disconnected during maintenance or service work.- This UPS contains potentially hazardous voltages.- Be aware that the inverter can restart automatically after the utility voltage is restored.- End user must follow applicable regional occupational safety codes/regulations during installation,operation and equipment maintenance. This may require additional field marking or labeling definingappropriate level of PPE (Personal Protection Equipment) to reduce the risk of Arc-flash related injuries.Contact our Technical Support for product specific information.INSTALLATION- This UPS must be installed and connected only by trained personnel.- Verify accurately during Commissioning and Maintenance of the UPS, for the following:Damaged components, squeezed wires and cables, or not correctly inserted plugs.- After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, arecorrectly reattached.- This UPS is intended for use in a controlled indoor environment free of conductive contaminants andprotected against animals intrusion.- WARNING! HIGH EARTH LEAKAGE CURRENT:Earth connection is essential before connecting to AC input!- Switching OFF the unit does not isolate the UPS from the utility.- Do not install the UPS in an excessively humid environment or near water.- Avoid spilling liquids on or dropping any foreign object into the UPS.- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104F(40°C).- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25C).- It is important that air can move freely around and through the unit. Do not block the air vents.- Avoid locations in direct sunlight or near heat sources.STORAGE- Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55C).- The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range -4°F (-20°C) to 104°F (40°C).- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (timedepending on storage temperature).BATTERY- The battery-voltage is dangerous for person’s safety.- When replacing the battery, use the same cells number, voltage (V), capacity (Ah).All the battery used, shall be of the same manufacturer and date of production.- Proper disposal or recycling of the battery is required.Refer to your local codes for disposal requirements.- Never dispose of battery in a fire: they may explode.- Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic.If exposed to electrolyte, wash immediately with plenty of water.- Avoid charging in a sealed container.- Never short-circuit the batteries.When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.- In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected and isolated.