1609716-01.2013-DGbFEITrCnDGBFEITRCN5| CommissioningCAUTION! Wear personal protective clothing such as goggles and protectivegloves!Make sure that the suction and discharge line valves are open.With the compressor switched off, add the liquid refrigerant directly to the condenser or receiver,breaking the vacuum.If the refrigerant needs topping up after starting the compressor, it can be topped up in vapourform on the suction side, or, taking suitable precautions, also in liquid form at the inlet to theevaporator.After starting, check the compressor's oil level.Drive motor in operating condition "High idle".Compressor run time min. 10 minutes.The system should have reached operating points.Check oil level. As the installation location of the compressor can differ in practice (inclinations), itis recommended that the oil level is checked in both sightglasses. The oil level must be visible inat least one sightglass.ATTENTION! Avoid overfilling the system with refrigerant!To avoid shifts in concentration, zeotropic refrigerant blends (e.g.R407C) must always be added to the refrigerating plant in liquidform.Do not pour liquid refrigerant through the suction line valve on thecompressor.It is not permissible to mix additives with the oil and refrigerant.5.5 Refrigerant charge5.6 Oil level check5.7 Shaft sealATTENTION! Failure to observe the following instructions can cause loss ofrefrigerant and damage to the shaft seal!INFO! The shaft seal seals and lubricates with oil. An oil leakage of0.05 ml per operating hour is therefore normal. This appliesparticularly during the run-in phase (200 - 300 h).To trap and collect leaked oil, the FK40 is fitted with an integratedleak oil trapping device with oil reservoir (P.6, Fig. 1).ATTENTION! After a compressor is replaced, the oil level must be checked again.If the level is too high, oil must be drained off (risk of oil impact,reduced performance of the air-conditioning system).