Q.uick Start GuideQ.brixx48Gantner Instruments Inc.USA | China | Singapore | India | Austria | Germany | France | Sweden1550 Hotel Circle N ∙ Suite 180 ∙ San Diego CA ∙ 92108 ∙ T +1 888 ∙ 512 ∙ 5788info.us@gantner-instruments.comwww.gantner-instruments.comCHANNEL CONFIGURATIONReal VariablesConfiguring a real variable is performed in ICP100 (included with test.commander).Double-click on a module to open the module in ICP100. For this example, we will usean A101 module.1. Double-click on the A101 module to open the module in ICP100:2. A new module will have the default settings loaded. For example, an A101 is a 2x channel universal input module. There are 16 x slots available in each module.If there are 2 x real variables used, there are 14 x remaining slots available forarithmetics, signal conditioning, set points, and alarms.3. Type: this column selects the type of variable (varies by module type). A realvariable is an AI (Analog Input), AO (Analog Output), DI (Digital Input), or DO(Digital Output).