Sec-4.8Section 4: ProgrammingMid-Stop Limit (Optional)OPENCLOSESTOPCALRUN SCROLLSCROLLSETCLEARMID-STOP CLRFig. 111. If operator is in RUN mode, press CAL/RUN to enter calibration mode.2. Press the CLOSE key to close the door to the down limit.3. Press SCROLL (up or down) until display reads “MID-STOP > CLR ” Fig.11• If display reads “MID-STOP > SET, Press the SET/CLEAR key to reset to “CLR”4. Press the OPEN key to open door to desired height.5. Press SET/CLEAR key to set mid-stop. Display will show “MID-STOP > SET”6. Press CAL/RUN key to return to RUN mode.NOTE: Setting of the MID-STOP should only be performed AFTER the Travel Limits and Max Run Timer settingshave been made.The MID-STOP feature must be turned off in order to properly set the Max Run Timer.CAUTION!ATTENTION!La fonction MID-STOP doit être désactivée afin de régler correctement la minuterie de course maximum.