2Notice!Install electrical leakage protector.Omission of installing electrical leakage protector can cause electric shock.DONíT install in place where flammable gas can easily leaks.Leakage of flammable gas can cause fire hazard.Water drainage pipe should be installed according to instructions to ensure smooth discharge ofwater. In addition, heat preservation measure should be taken to prevent moisture condensation.Improper installation of drainage pipe can cause water leakage and possibly damp or soak indoorarticles.Selection of installation placeRequirementsAvoid installing in the following places:Where is of high salinity (coastal areas).Where is of high sulfide gas (thermal springareas).(Use in the above areas can easily result indefects of the machine and need specialmaintenance.)Where oils (including mechanical oils) easilysplatter and vapor is abundant.Where organic solvents are uses.Where thereís equipment emittingelectromagnetic waves of high-frequency nearby.Where ceilingís height is over 3 m.Where windows and doors are exposed tooutdoor air of high humidity.Insulation of metal parts of building and airconditioner should be carried on in compliancewith technical standards of electrical appliancesand facilities.Installation place for indoor subassembly shouldbe of evenly circulating cool and hot air.Confirmation of installation location and spaceEnsure selected place is enough for space ofinstallation and maintenance. (Here we only usesimple drawing as figurations of the series aredifferent)Note: Here we only use simple drawing asfigurations of the series are different1.2.3.Machine(horicontal&front view)horicontal&side view)(Lower in the back)>300mm >300mmDon't put anyobstacles nearthe wind inlet.>500mm>20mm