INSTALLATION MANUAL FOR OUTDOOR UNIT22Blow outAbsorb in Absorb inAbsorb inWorking, repair surfaceA vertical view of the outdoor unitOver 300mmOver 20mmOver20mmOver20mmOver20mmOver1000mm(front side)Wire ropeProtection cushionBase panelWire ropeM12 foot screw bolt4 screws each unitWarningSelection of installation siteIt should be installed at places where it is firm enough to withstand the weight of the air conditioner toprevent falling.Typhoon and earthquake prevention. It should be installed according to specific requirements.Inasppropriate installation may lead to accidents.Note: Obstacles should be 2000mm off the top of the out-door unit. Obstacles nearby should be 400mm lowerthan the top of the unit.1. HandingAs there is no protective package for the outdoor unit,sothe following points merit attention:(1) When forklift is used, insert the fork into the holes inthe base plate.(2) When crane is used, lift the unit with 4 pieces of steelrope with diameter above 6 mm.(3) Put protective materials between the cable and theunit to prevent deformation and damage of the surface.2.Mounting(1) The distance between two connectionsmust not beless than 20mm.(1)During installation, connect the outdoor unit and alignthe mounting surface(See the figure on the right).Mountthe electric distribution device on the external side ofthe unit in accordance to the installation instructions forelectric distribution device.(2)To ensure good performance of the machine and facili-tate installation and maintenance, adequate space mustbe reserved (See figure on the right).Installtion space