Service diagnosis31 Domestic air conditioner10.3.3 Indoor AC fan motor malfunctionIndoor Display ■ □ ★ / E14Method of The rotation speed detected by the Hall IC during fan motor operation is used to determineMalfunction abnormal fan motor operationDetectionMalfunction when the detected rotation feedback signal don’t received in 2 minutesDecisionConditionsSupposed ■ Operation halt due to breaking of wire inside the fan motor.Causes ■ Fan motor overheat protection■ Operation halt due to breaking of the fan motor lead wires■ Detection error due to faulty indoor unit PCBTroubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or elseparts damage may be occurred.Check whether terminalson indoor pcb is well ?Electrify the machine again and turn it on in the cooling operation,Measure voltage between the positions 1and 3 of Terminal CN5on the indoor PCBthe voltage is about 90-220vaccheck whether motor can runwhen turn on the unitthe indoor motor is damaged and need replaceYesNONOYes Measure whether there is voltage pulse (0-5VDC)between the positions middle wire and black wireof Terminal CN2 on the indoor PCBNOthe indoor pcb is damaged and need replacePull out the terminals on the indoormainboard and reinsert them.NoYesIs it ok?Yes