Outdoor unitForced fastening without careful centeringmay damage the threads and cause aleakage of gas.Pipe Diameter ( )Liquid side 6.35mm(1/4")Gas side 9.52mm(3/8")Fastening torque18N.m40N.mGas side 12.7mm(1/2") 55N.mCAUTIONIn case more than 5mOil trap shoud be installed every 5~7mMax. Length:A=15m (for:07k 09k 12k)A=25m(for:18k 22k)Max.Elevation:10m15m(for:18k 22k) no more gas if the length of connecting pipe is less than 7mAOutdoor unitIndoor unitOutdoor unitIndoor unitOil trap(for:07k 09k 12k)1.Installation of Outdoor Unit3.Connection4.Attaching Drain-Elbow2.Connection of pipesInstall according toTo bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radiusshould be 30 to 40 mm or longer.Connecting the pipe of gas side first makes working easier.The connection pipe is specialized for R410A.Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.The standard pipe length is 5m. If it is over 7m, the function of the unit will be affected. If the pipe hasto be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerantmust be conducted by professional air conditioner engineer. Before adding additional refrigerant,perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then chargeadditional refrigerant.Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully intoterminal block, then tighten the screws.If wiring is not correct, proper operation can not be carried out and controller may be damaged.If the drain-elbow is used, please attach it asfigure. (Note: Only for heat pump unit.)Drawing for the installation of indoor and outdoor unitsInsert the cable according to terminal number in the same manner as the indoor unit.Fix the cable with a clamp.Half union Flare nutSpanner Torque wrench6no more gas if the length of connecting pipe is less than 10m(07k 09k 12k)(18k 22k)