Indoor unitFix to side bar and lintel a mounting bar, Which is separately sold, and thenƽfasten the plate to the fixed mounting bar.Refer to the previous article, “ When the mounting plate isƽposition of wall hole.Make a hole of 60 mm in diameter, slightly descending to outside the wall.ƽInstall piping hole cover and seal it off with putty after installationƽWhen the mounting plate is first fixed1. Carry out, based on the neighboring pillars or lintels, ato be fixed against the wall, then temporarily fasten the plate with one steel nail.2. Make sure once more the proper level of the plate, by hanging a thread with aweight from the central top of the plate, then fasten securely the plate with theattachment steel nail.3. Find the wall hole location A using a measuring tapeA=145mm30mmWhen the mounting plate is fixed side bar and lintel Fitting of the Mounting Plate and Positioning of the wall HoleLid for rightpipingLid for under piping pipeFix with adhesive tapeLid for left pipingIndoor/outdoor electric cable and drain hose must be bound with refrigerantƽpiping by protecting tape.[ Other direction piping ]Cut away, with a nipper, the lid for piping according to the piping direction andƽthen bend the pipe according to theposition of wall hole. When bending, becareful not to crash pipes.Connect beforehand the indoor/outdoor electric cable,ƽ and then pull out theconnected to the heat insulation of connecting part specially.proper leveling for the platefirst fixed “, for the Making a Hole on the Wall and Fitting the Piping Hole CoverDrawing of pipe Installation of the Indoor Unit[ Rear piping ]Draw pipes and the drain hose, then fasten them with the adhesive tapeƽ[ Left Left-rear piping ]In case of left side piping, cut away, with a nipper, the lid for left piping.ƽIn case of left-rear piping, bend the pipes according to the piping direction toƽthe mark of hole for left-rear piping which is marked on heat insulation materials.1. Insert the drain hose into the dent of heat insulation materials of indoor unit.2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull itout on the front side, then connect them.3. Coat the flaring seal face with refrigerant oil and connect pipes.Cover the connection part with heat insulation materials closely, and make surefixing with adhesive tapeFixing the indoor unit bodyHang surely the unit body onto the upper notches of theƽmounting plate. Move the body from side to side to verify itssecure fixing.In order to fix the body onto the mounting plate,hold upƽthe body aslant from the underside and then put it downperpendicularly. Connecting the indoor/outdoor Electric CableRemoving the wiring coverRemove terminal cover at right bottom corner of indoor unit, then takeƽoff wiring cover by removing its screws.1. Insert from outside the room cable into left side of the wallhole, in which the pipe has already existed.2. Pull out the cable on the front side, and connect the cablemaking a loop.Note When connecting the cable, confirm the terminal number of indoor andoutdoor units carefully. If wiring is not correct, proper operation can notbe carried out and will cause defect.Insert the cable from the backƽ side of the unit, then pull it out on the front side.Loosen the screws and insertƽ the cable ends fully into terminal block, thentighten the screws.Pull the cable slightly toƽ make sure the cables have been properly inserted andtightened.After the cable connection,ƽ never fail to fasten the connected cable with thewiring cover.mounting plateWhen connecting the cable after installing the indoor unitWhen connecting the cable before installing the indoor unitWhen you unload the indoor unit,please usethen lift the bottom of the body outwardslightly and lift the unit aslant until itleaves the mounting plate.agraffe mounting plateUnloading of indoor unit bodyƽyour hand to arise the body to leave agraffe,Remote controller (1)R-03 dry battery (2)Mounting plate (1)Drain hose (1)Ø4X25 Screw (4)Plastic cap (4)Drain-elbow (1)Cushion (4)Pipe supporting plate (1)Accessory partsLiquid pipe (Ø) 6.35mm(1/4”)Gas pipe (Ø) 9.52mm(3/8”)NOTE˖The thickness of the pipe must be 0.8mm at least.Selection of pipe2A=145mmB= 60mmØ30mmB= 60mmØIndoor side Outdoor sideØ60mmWall holeThickness of wall(Section of wall hole) Piping hole pipeGHeat insulationmaterialDrain hosePipingPipe supportingplateIndoor/outdoor electric cable