Air Conditioner Edition:2006/01/09Outdoor unit1.Installation of Outdoor Unit3.Connection4.Attaching Drain-Elbow2.Connection of pipesInstall according toTo bend a pipe, give the roundness as large as possible not to crush the pipeConnecting the pipe of gas side first makes working easier.The max vertical distance between the indoor unit and the outdoor unit is 5 m.Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully intoterminal block, then tighten the screws.If wiring is not correct, proper operation can not be carried out and controller may be damaged.If the drain-elbow is used, please attach it asfigure. (Note: Only for heat pump unit.)Forced fastening without careful centeringmay damage the threads and cause aleakage of gas.Pipe Diameter ( )Liquid side 6.35mm(1/4")Gas side 9.52mm(3/8")Fastening torqueDrawing for the installation of indoor and outdoor unitsInsert the cable according to terminal number in the same manner as the indoor unit.Fix the cable with a clamp.18N.m40N.mHalf union Flare nutSpanner Torque wrenchGas side 12.7mm(1/2") 50N.mOutdoor unitGas side 15.88mm(5/8") 60N.mBe careful that matters, such as wastes of sands, etc. shall not enter the pipe.37