ENGLISHPAGE 8 INSTALLATION REQUIREMENTSELECTRICAL REQUIREMENTS cont.POWER SUPPLY CORD (See Fig.2)Wiring RequirementsFor model HWE15XCN• 115-volt (103.5 minimum to 126.5 maximum)• 15-amp time-delay grounded fuse or circuit breaker• Use on single outlet circuit only.For model HWE18VCN• 230/208 volt (187 min. to 253 max.)• 15-amp time-delay fuse or circuit breaker• Use on single outlet circuit only.For model HWE24VCN• 230/208 volt (187 minimum to 253 maximum)• 20-amp time-delay grounded fuse or circuit breaker• Use on single outlet circuit only.REQUIRED GROUNDING METHOD (See Fig.2)This air conditioner must be grounded. This air conditioner is equipped with a power supplycord that has a 3 prong grounding plug. The power supply cord must be plugged into a mating,grounded 3 prong outlet, and grounded in accordance with all local codes and ordinances. If amating outlet is not available, it is the customer’s responsibility to contact a qualified electricianand ensure that a properly grounded 3 prong outlet is installed.POWER SUPPLY CORD (See Fig.3)NOTE: Your air conditioner's plug may differ slightly in appearancefrom the one shown.A. Reset buttonB. Test buttonThis room air conditioner is equipped with an a leakage current detection interrupter (LCDI)power supply cord required by UL. This power supply cord contains a current detection device.If the power supply cord is crushed, this device will detect current leakage and power will bedisconnected from the air conditioner. If this power supply cord is damaged, it cannot berepaired and must be replaced with a cord from the product manufacturer. If the power supplycord is damaged call Haier Customer Service: 1-877-337-3639.RESETTESTABFig. 3Fig. 2HWE15XCNHWE18VCNHWE24VCN115V15 Amp 230V15 Amp115V15 Amp 230V15 Amp 230V20 Amp115V15 Amp 230V15 Amp 230V20 Amp