7PC 45 Corn/Pellet StoveVentingRequirements for Terminating the VentingWARNING: Venting terminals must not be re-cessed into a wall or siding.NOTE: Only PL vent pipe wall pass-throughsand fire stops should be used when venting throughcombustible materials.NOTE: Always take into consideration the ef-fect the prevailing wind direction or other wind cur-rents will cause with flyash and /or smoke when plac-ing the termination.In addition, the following must be observed:A. The clearance above grade must be a mini-mum of 18".1B. The clearance to a window or door that maybe opened must be a minimum of 48" to the side,48" below the window/door, and 12" above the win-dow/door.1( with outside air installed, 18” )C. A 12" clearance to a permanently closedwindow is recommended to prevent condensationon the window.D. The vertical clearance to a ventilated soffitlocated above the terminal within a horizontal dis-tance of 2 feet (60 cm) from the center-line of theterminal must be a minimum of 18".E. The clearance to an unventilated soffit mustbe a minimum of 12".F. The clearance to an outside corner is 11"from center of pipe.G. The clearance to an inside corner is 12".H. A vent must not be installed within 3 feet (90cm) above a gas meter/regulator assembly whenmeasured from the horizontal center-line of the regu-lator.1I. The clearance to service regulator vent outletmust be a minimum of 6 feet.1J. The clearance to a non-mechanical air sup-ply inlet to the building or the combustion air inlet toany other appliance must be a minimum of 48”.1K. The clearance to a mechanical air supplyinlet must be a minimum of 10 feet.1(with outside air installed, 6 feet )L. The clearance above a paved sidewalk or apaved driveway located on public property must bea minimum of 7 feet.1,2M. The clearance under a veranda, porch, deckor balcony must be a minimum of 12 inches.1,3NOTE: The clearance to vegetation and otherexterior combustibles such as mulch is 36” as mea-sured from the center of the outlet or cap. This 36”radius continues to grade or a minimum of 7 feetbelow the outlet.1Certain Canadian and or Local codes or regu-lations may require different clearances.2A vent shall not terminate directly above a side-walk or paved driveway which is located betweentwo single family dwellings and serves both dwell-ings.3Only permitted if veranda, porch, deck, or bal-cony is fully open on a minimum of 2 sides beneaththe floor.NOT E: Where passage through a w all, orpartition of combustible construction is desired,the installation shall conform to CAN/CSA-B365.(if in Canada)V A= Vent terminal = Air supply inletFixedClosedOpenableOpenable FixedClosedInside CornerDetail= Area where terminal is not permitted