GW-7472 / GW-7473 User Manual, Version 2.5, June 2014 --- 45Configurations: “Static IP Address”, “Subnet Mask” and “Default Gateway”. The defaultEthernet settings are shown below.Table 5.1 network settingsItem Settings (Init Mode)IP 192.168.255.1Gateway 192.168.0.1Mask 255.255.0.03. Modbus RTU Configurations: “Net ID”, “Baud Rate”, “Data Bits”, “Stop Bits” and“Parity”, The default Modbus settings are shown below.Table 5.2 Modbus settings4. Click “Submit” to finish the configurations.5.2.2 EtherNet/IP Adapter1. Users can set the EtherNet/IP adapter information to the GW-7473 with “AdapterSettings” window. There are “Static IP Address”, “Input Instance” and “Output Instance”.Figure 5.1 Adapter settingsIn the “input instance” and “output instance” window, Users must to fill out “Instance ID”and “instance size”. The Instance size is equal to the sum of I/O status size. Users canalso modify the I/O status size and their start address at the EtherNet/IP packet.For example, we want to add an EtherNet/IP adapter (EIP-2055) to the adapter menu.Item Settings (Init Mode)Net ID 1Baud Rate 115200Data Bits 8Stop Bits 1Parity None