➤ For other application conditions, check conductor diameters and change accordingly.Other conditions would include, for example:■ Higher temperature■ Other cable installation method■ Cable length >50 m2.14.1 Mains frequency: 50 HzRated voltage: 200V±10%/3/50HzASK 27 ASK 32 ASK 35Backup fuse [A] 80 100 100Supply cable [mm2] 4x25 4x35 4x35Current input [A] 69 83 91Tab. 23 Mains supply 200V/3/50HzRated voltage: 230V±10%/3/50HzASK 27 ASK 32 ASK 35Backup fuse [A] 80 80 100Supply cable [mm2] 4x25 4x25 4x35Current input [A] 61 72 79Tab. 24 Mains supply 230V/3/50HzRated voltage: 400V±10%/3/50HzASK 27 ASK 32 ASK 35Backup fuse [A] 40 50 50Supply cable [mm2] 4x10 4x10 4x10Current input [A] 35 38 45Tab. 25 Mains supply 400V/3/50Hz2.14.1.1 Network conditionsThe network conditions apply to machines connected to public mains supplies with the followingcharacteristics.■ Mains frequency 50 Hz■ Voltage between exterior and neutral lines 220 V...250 V■ Voltage between the exterior lines 380 V...440 VThey do not apply to private power supplies within industrial areas isolated from the public mains.Machines with current consumption >16 A...≤75 A comply fully with IEC 61000-3-12.The machines listed in table are intended for operation with a public power supply with a networkimpedance at the transfer point (house connection) of maximum Zmax [Ohm].2 Technical Specifications2.14 Power supply specifications12 Service Manual Screw CompressorASK T SIGMA CONTROL BASIC 9_5717 20 E