Heater Location Instructions:Arrange the heater so the hot discharge air is:1. Free of interference from any items that could block or disrupt theairflow reaching the farthest point of the area being heated.2. Direct the airflow along the coldest part of the garage area withoutblowing the heat directly at the wall or warming the items in any way.Typically a distance of 3 to 4 feet is away from walls or cabinets isacceptable.3. Do not blow directly on stationary people in the room or workareas.4. Smaller rooms will be comfortably heated with one unit. Largerrooms may require multiple heaters Moves the air in a circular, wallwiping pattern around the room. This configuration aids in pre-heating the incoming air of the next heater and will raise the roomtemperature faster. See Fig 3.4 and 3.5Thermostat:The inbuilt thermostat has a range of 40 to 90 degrees F and whenset will keep the room at a comfortable temperature. We recommendexperimenting with settings to determine ideal room temperaturewhile occupied and unoccupied. Once those ideals are identified,mark the settings on the label with a felt tip marker.If a remote line voltage thermostat is used it should be rated forhigher than the amp load of the heater connected. Locate the ther-mostat 5 ft. (1.5 m) above the floor on an interior wall away from colddrafts, cold steel posts, outside walls, hot water pipes, hot lights andaway from the discharge air stream of the heater.Ceiling MountMounting Instructions3Wall MountTypical garage with 2 or 3 outside wallsLarger garage with all outside wallsor colder climateHeater may be mounted to the wall or ceiling. For best performance and sat-isfactory results the heater should not be mounted over 10 feet high off thefloor. Minimum distance off the floor is 6 ft. per UL standards 2021.For wall installation the bracket must have the hook end pointing up so if theheater were to loosen over time it would not fall out. See Fig 3.3Wall stud and ceiling joists are typically wider than our mounting bracketwhich is 11 inches wide. The heater weighs 14 lbs. and should be mountedonto at least one stud to be properly supported.Your fasteners penetrating a stud is critical to supporting the weight. A gyp-sum wall board fastener is not strong enough. But if your ideal location has nosolid backing. You can fasten with large screw fasteners a 2 x 6 across thestuds or ceiling joists and attach the heater then to the 2 x 6. This works forceiling or wall mounting. Attach with appropriate lag bolts with proper depthfor the 14 lbs. Install hex fasteners into both sides of heater with washer onthe outside of the bracket and star washer between the heater and bracket.Minimum clearances from walls and ceiling6 inches / 15.24 cm to the side5 inches / 12.7 cm from the back2 inches / 5.08 cm from ceilingNever point heater at ceilingMaintain clearance of at least 3 ft. in front of heat outletFig 3.3Fig 3.1 Fig 3.4Fig 3.5Fig 3.2UPSAVE THESE INSTRUCTIONSAfter bracket is mounted, place washerson bolts and then in heater sides. Droponto bracket slots placing lock washerbetween heater and bracket and washerbetween bracket and bolt. Adjust to thepreferred angle and tighten bolts to 30 ft.lbs. of torque minimum.Mounting boltFlat washeroutside bracketStar WasherInside bracket