1. IntroductionThe Syncro Focus/Focus+ LCD repeater is a display and control unit which duplicates theindications and primary controls of Syncro fire alarm control panels connected to the same network.The repeater connects to the control panel via the network interface and requires that the maincontrol panel have an S555 network card fitted. For full details of Syncro networking refer to SyncroNetworking Manual.The repeater is connected to the network and any number of repeaters can be connected up to themaximum number of nodes allowed by the network specification, which is 64 (including controlpanels).In addition to displaying the status of the fire alarm system, the repeater can provide limited localcontrol functions via local control outputs.2. SafetySuppliers of articles for use at work are required under section 6 of the Health and Safety at Workact 1974 to ensure as reasonably as is practical that the article will be safe and without risk to healthwhen properly used.An article is not regarded as properly used if it is used ‘without regard to any relevant information oradvice’ relating to its use made available by the supplier.This product should be installed, commissioned and maintained by trained service personnel inaccordance with the following:(i) IEE regulations for electrical equipment in buildings(ii) Codes of practice(iii) Statutory requirements(iv) Any instructions specifically advised by the manufacturerAccording to the provisions of the Act you are therefore requested to take such steps as arenecessary to ensure that you make any appropriate information about this product available toanyone concerned with its use.The mains powered version of this equipment is designed to be operated from 230V 50Hz mainssupplies and is of class 1 construction. As such it must be connected to a protective earthingconductor in the fixed wiring of the installation and a readily accessible double pole disconnectdevice shall be incorporated in the fixed wiring.Failure to ensure that all conductive accessible parts of this equipment are adequatelybonded to the protective earth will render the equipment unsafe.3. InstallationInstallation of the repeater should be carried out by qualified personnel only.The electronic components within the repeater are vulnerable to physical damage and damage byelectrostatic discharges.It is advisable to wear a wrist strap designed to prevent the build-up of static chargeswithin the body, before handling any electronic circuit boards.Never insert or remove boards or components with the power on.Mounting the CabinetThe site chosen for the location of the panel should be clean and dry and not subject to shock orvibration.The temperature should be in the range -5° to +35° C, the humidity should not exceed 95%.Using the box as a template, mark the position of the fixing holes, ensuring that the wall is flat atthe chosen location.Drill and plug the wall then fix the cabinet using all fixing points.Man-1081_Syncro_Focus+_04 Page 3 of 13