LB-762 Controller Installation Manual LAB-EL1.5 Cooperation with LB-760 regulatorsLB-762 regulators can be used in systems where LB-760 regulators have been used so far. It is possible to build one commonsystem in which both types of regulators operate to provide performance of respective system functions regardless of thetype of regulator (such as common measurement of external air parameters and collective CO2 concentration measurementsystem).Unfortunately owing to software incompatibility between the regulators and inconsistency of communication protocols itis impossible to use a common RS-485 network for both types of regulators. LB-760 type regulators must have its ownRS-485 network, while LB-762 regulators must have their own, separate network. If LB-762 regulators use Ethernet, thiswill necessarily be a separate network. If LB-762 regulators are connected by means of RS-485, one should route a separateRS-485 network cable for LB-762 regulators.Figure 1.5 presents a scheme of a sample common installation with LB-762 and LB-760 type regulators, using RS-485 networkfor LB-762. The scheme with Ethernet network is analogous - LB-760 regulators remain connected by RS-485 network, whilefor LB-762 RS-485 network should be replaced with Ethernet network.