132.2 The Front Panel DisplayAfter the ESCR has completed start up, the “AC ON” LED on the front panel and either the “FLOAT” or “EQUALIZE” LEDon the front panel will be lit. The LCD will display the system DC output voltage and DC output current on line one. Linetwo of the LCD displays the status of ESCR.Figure 13 - Front Panel Display (Unit in Float Mode)2.2.1 ControlsUp/Down Arrows – The Up and Down arrows offer no function outside of Configure Mode. When in Configure Modethe up and down arrows allow the customer to navigate menus and increase or decrease values.Float/Equalize Button – The Float/Equalize Button allows the user to manually switch between float mode and equalizemode. When the ESCR is in equalize mode, line two of the display will switch between “EQUALIZE MODE” and the timeremaining.Lamp Test Button – The Lamp Test button allows the user to check the function of all of the Front Panel LEDs withoutaffecting the operation of the charger. While the lamp test is running all of the LEDs flash and a sequence of numbers iswritten to the display.Reset/Back Button – Under normal system operation, the Reset/Back Button operates as the reset button. Pressingreset allows the user to restart the ESCR. Upon restarting, the ESCR will once again go through the start-up sequencedescribe in section 2.1.3. In the Configure mode the Reset/Back button operates as the back button. Pressing the backbutton allows the user to navigate to a previous screen or out of the configuration.Configure/OK Button – In Configure Mode, the charger is turned off, and there will be no output. The Configure/OKbutton brings the ESCR into Configuration Mode, allowing the user to set charger parameters in Basic Settings as well asFloat Voltage, Equalize Voltage, Equalize Timer, Current Limit, Temperature Compensation and Alarm settings. Once inConfiguration Mode, this button becomes the OK button which is used to make selections within the menus.