6810 Accessories10.7 Fiber OpticThe LAMTEC Fiber Optic System is available with 2 spectral sensitivities and 2 basicmechanical constructions.The spectral sensitivity is matched to the LAMTEC flame detector.WARNING!F200K IR-x FOThe flame detector F200K FO in the IR version (IR-1..4) may only be used with theLAMTEC Fiber Optic in the IR version. The Fiber Optic IR version includes the requiredspectral sensitivity limitation.Visible is the Fiber Optic IR version on the process optics (see Fig. below).The viewing port to the flame is not a lens, but covered with a black filter.Fig. 10-28 Fiber optic rigid with Flame scannerFiber Optic with enclosure - Type key: FOabb-cc-dda - enclosure type: R - rigid, F - flexibleb - enclosure series: e.g. 10c - lenght: e.g. 25 - (2,5 m)d - optic: UV - uv/vis/nir, IR - nirTechnical Data AK01-51 Used for UL Listed Section and hazardous area Class I Division 2Protection class TC-ER (Tray Cable Exposed Run), outdoorHousing material Outer sheath of special PVCMinimum bending radius Static/Occ. moved: 6/20 x OD (Outer diameter)Temperature range Static/Occ. moved: -40/-10 °C ... +90 °C / -40/+14 °F ... +194 °FCross-section 8 × 0,9 mm 2 / 18 AWGShild copper braidingCore identification black cores with continuous white numbering1 Component Group Process Optics 3 Component Group housing1.1 Optic UV 4 Component Group burner mounting assembly1.2 Optic IR 5 Component Group Flamescannerholder assembly FV30-FO2 Fiber bundle (customer-specific length)