EN244. TECHNICAL DATAMeasuring RangesInput type Indication range(rated range) classPT100 -200...850 ºC (-200...850 ºC)0.1PT1000 -200...850 ºC (-200...850 ºC)400 Ω 0...440 Ω (0...400 Ω)4000 Ω 0...4040 Ω (0...4000 Ω)Thermocouple type E -205...1000 ºC (-200...1000 ºC)Thermocouple type J -205...1200 ºC (-200...1200 ºC)Thermocouple type K -205...1372 ºC (-200...1372 ºC)Thermocouple type N -205...1372 ºC (-200...1372 ºC)Thermocouple type R -50...1768 ºC (-50...1768 ºC)Thermocouple type S -50...1768 ºC (-50...1768 ºC)Voltage input 60 mV -75...75 mV (-60...60 mV)Voltage input 150 mV -155...155 mV (-150...150 mV)Voltage input 300 mV -310...310 mV (-300...300 mV)Voltage input 10 V -13...13 V (-10...10 V)Current input 0...20 mA -24...24 mA (-20...20 mA)Current input 4...20 mA 3.6...22.0 mA (4...20 mA)Current time 00.00...23.59 ±20 ppmMeasuring loops parameters• Current in the sensor circuit during the resistance measurements 175 μA• Input resistance for voltage measurements: thermocouples, 60 mV,150 mV, 300 mV, 0...10 V > 1 MΩ• Input resistance for the current ranges < 11 Ω• Test leads resistance compensation range (maximum resistance of asingle lead) < 20 Ω• Terminals temperature automatic compensation range for measure-ments using the thermocouple sensors -30...80 ºC