2. INSTALLATION3. Installation, continuedWiring the Inverter AC Input (refer to diagrams on the following pages) Remove the chassis ACaccess cover to access the internal terminal block.Route the cable and conduit from the main panel, approved bypass selector switch or mainAC panel to the inverter’s AC INPUT conduit clamp. Tightenthe clamp securely on the conduit. Always leave a little extra slack in the wiring.Connect the hot wire (BLACK) from the main panel’s dedicated 30 amp breaker to the“AC INPU T (HOT 1 IN)” terminal. Tighten the screw terminal to 16 inch-p o u n d s .NOTE: If using dual inputs, connect the RED wire from the main panel to AC INPUT(HOT 2 IN)Connect the neutral (WHITE) from the main panel’s neutral bus bar to the “ACINPUT (NEU)” terminal. Tighten the screw terminal to 16 inch-p o u n d s .Connect the ground (GREEN) wire from the main panel’s neutral bus bar to the “GROUND”terminal. Tighten the terminal to 16 inch-p o u n d s .Wiring the Inverter AC Output (refer to diagrams on the following pages) Route the cable andconduit from the AC distribution panel to the inverter’s AC OUTPUT conduit clamp.Tighten the clamp securely on the conduit.Connect the hot (BLACK) wire to the “AC OUTPUT 1 (HOT)” terminal. Tighten theterminal to 16 inch-pounds.NOTE: If using dual outputs, connect the RED wire to the “AC OUTPUT 2 (HOT)”terminal.Connect the neutral (White) wire to the “AC OUTPUT (NEU)” terminal. Tighten theterminal to 16 inch-pounds.Connect the ground (Green) wire to the “GROUND” terminal. Tighten the termi nal to16 inch-pounds.Final InspectionVerify all cables / conduit runs are secured with wire ties or other nonconductivefasteners to prevent chafing or damage from movement and vibration.Verify strain reliefs or grommets are in place to prevent damage to the wiring or conduit where itpasses through walls, bulkheads or other openings.Verify all AC connections are correct and torqued to 16 inch pounds.Replace the covers on the main electrical / distribution panel. Replacet h e chassis access cover.Verify the inverter’s front panel switch is in the "OFF" position.NOTE: If required by code, have the installation inspected by an electrical inspector.Ó 2003 - Magnum Energy, Inc. 21