28 Part Number 000014141 Rev 08 5/21Installation Section 2When lengthening or shortening lines,follow good refrigeration practices, purgewith nitrogen and insulate all tubing. Donot change the tube sizes. Evacuate thelines and place about 5 oz (145 grams) ofvapor refrigerant charge in each line.1. Remove the dust caps from the lineset, condenser and ice machine.2. Apply refrigeration oil to the threadson the quick-disconnect couplersbefore connecting them to thecondenser.3. Carefully thread the female fitting tothe condenser or ice machine by hand,then tighten the couplings with awrench until they bottom out.4. Turn an additional quarter turn toensure proper brass-to-brass seating.Torque to the following specifications:Liquid Line Discharge Line10 - 12 ft lbs13.5-16.2 N•m35 - 45 ft lbs47.5-61.0 N•m5. Check all fittings and valve caps forleaks and reinstall and tighten caps.6. Interconnecting line voltage wiringis used to energize and de-energizethe condenser fan motor. The remotecondenser voltage matches the icemachine head section voltage.Interconnecting Wiring ConnectionsIce Machine Remote CondenserL1 F1L2 F2Installation is finished for remotecondenser models. Proceed to page 32for start-up procedure.QUIETQUBE® MODELS WITH CVDTECHNOLOGY™Step 1 Secure the Condensing Unit.Through-holes are provided to secure thecondensing unit to a curb, rack or woodentimber.Step 2 Route the Refrigeration Tubing.Route the refrigeration tubing betweenthe ice machine head section and thecondenser or CVD condensing unit.• A suction line oil trap is required whenrise is more than 20 feet (6 meters).• Only one trap is allowed in the line set.• Shorten the line set as required, do notcoil line set.Manitowoc S-Trap KitModel S-Trap KitNumberTubingSizeIBF0620C IBF0820CIBT1020CIF0600C IF0900CIT1200CK00172 5/8 inch(16 mm)IF1400C IF1800CIF2100C K00166 3/4 inch(19 mm)• Maximum amount of time therefrigeration system can be exposed tothe atmosphere is 15 minutes.• Purge line set with dry nitrogen whilebrazing.• Shutoff valves for the line set on the icemachine must remain closed and beprotected from heat during brazing.• The condensing unit ships with a 50/50mixture of nitrogen/helium.