LIBRA LIB-P432EX Series Programming Instructions NAPCO Security SystemsPage 12EXIT DEALER PROGRAM MODE: This completes the custom default program. Press the y button to enter the DirectAddress Program Mode for further programming or press y once again to end all programming and resume normal keypadoperation.Clear Dealer Program (Erases Dealer Program)This erases the dealer program. Use this feature to start a customized default program. ProgramData and System Status Memory is erased where Scheduled Data and Zone Descriptions aremaintained.Access address 2285, then press the u button. Data entry is not allowed. NOTE: Enter Easy MenuDriven Program Mode to program system again.Cold Start (Erases Entire Program)This erases the entire program including Dealer Program by erasing Program Data, Zone DescriptionData and System Status Data (similar to a new panel).Access address 2286, then press the u button. Data entry is not allowed. NOTE: Some features(schedules) can only be programmed again with the Downloading Software.(Direct Entry)2285 XX(Direct Entry)2286 XXCLEAR PROGRAM: Should it be necessary to create a new custom default program, (a) from the Dealer Program Mode, pressy to enter the Address Program Mode; (b) access Location 2285 (Clear Program) or 2286 (Cold Start); (c) press u and then(d) press y to exit the Dealer Program Mode. A “SYSTEM TROUBLE/E09-00 SERVICE” will occur. Press y to silence thekeypad.