2 StarLink ™ SLE-LTE Commercial Series Alarm Communicators -- Installation InstructionsNOTICE TO AUTHORITIES HAVING JURISDICTION, USERS, INSTALLERS,DEALERS, AND OTHER AFFECTED PARTIESUnattended Remote Downloading No Enable / DisableDisabled (Jumper 1 installed). Also required for Commercial / Burgla-ry installations. Note: See page 7 "Configuration Download / Firm-ware Updates" for jumper instructions.IN2 and IN3 Unsupervised Yes Supervised / UnsupervisedUnsupervised using conduit within 20 feet of FACP (default). If notusing conduit, install Jumpers 4 and 5 and EOL Resistors (see pages3 and 4).7 Day Supervision, Radio to NOC No 200 seconds, 5 minutes,60 minutes, 7 days 200 seconds, 5 minutes, 60 minutesFIRE PROGRAMMING OPTION PERMITTED INUL864? (Y/N) AVAILABLE SETTINGS REQUIRED UL 864 SETTINGSed inside its own housing compartment with a replaceableUL Listed .5A fast blow primary fuse. 120VAC connectionsare to be made by a licensed electrician using suitable con-nectors, in accordance with N.E.C. and local code require-ments.ADDITIONAL COMPONENTSIn addition to the models listed above, the following sub-assemblies are available:SLE-ULPS-R - Power Supply. Required for installationswhere the control panel cannot provide the 71mA ofAuxiliary power required to operate the StarLink radio.Uses a standard 4AH / 12V minimum (7AH maximum)rechargeable battery to provide radio standby power.Requires connection to either the model NAPCOTRF12/T123 (16.5V / 20VA) external plug-in transformeror the chassis-mounted 16.5VAC / 20VA transformeraffixed inside the housing (see wiring diagrams further inthis manual). Note: For models without the SLE-ULPS-R, connect the radio terminals 1 and 2 to the controlpanel Aux Power terminals (observing polarity).SLE-DLCBL - Download Cable, 6 feetSLE-ANTEXT30 - Extended antenna with 30 feet of cableSLE-ANTEXT50 - Extended antenna with 50 feet of cableSLE-ANTEXT75 - Extended antenna with 75 feet of cable(Any suitable external cellular antenna is permitted byUL). Always follow the manufacturer's installation in-structions. Note: Antennas are not Listed by UL. ForLTE radios where an External Antenna needs to be in-stalled outside of the room in which the radio is installed(maximum 30 meters (98 feet) in Residential applica-tions), please use RF Transmitter Board9SLELTEEXAPSLD available from our Customer Ser-vice Department, if not provided. The9SLELTEEXAPSLD is identified by "two red dots" locat-ed on the lower right corner of the board. See WI2239included with the 9SLELTEEXAPSLD for the simple in-stallation procedure.GEM-Tamperkit - Tamper switches and screws to protectmetal housing (see page 18).SPECIFICATIONSThe following specifications apply to all StarLink radio mod-els unless otherwise stated:Electrical Ratings for 120VAC, 60HzFor Models with Power Supply Input Voltage: 120VAC nominal Input Current: 150mA maximum Maximum Charging Current: 200mAElectrical Ratings for +12VFor Models without Power Supply* Input Voltage: 10-15VDC (power-limited output fromListed control panel). Note: Model SLE-LTEV-CFB israted 10-25VDC input. Input Current for SLE-LTEV-CB: 10V = 90mA, 12V =71mA, 15V = 63mA, with peak RF transmission currentof 200mA. Input Current for SLE-LTEV-CFB: 10V = 90mA, 12V =71mA, 25V = 68mA, with peak RF transmission currentof 200mA.Electrical Ratings for the IN 1 Burg/Fire Input: Input Voltage: 9-15VDC. Note: Model SLE-LTEV-CFBis rated 9-25VDC input. Maximum Input Current: Up to 2mA from FACP NACcircuitElectrical Ratings for IN 2 and IN 3: Maximum Loop Voltage: 15VDC. Note: Model SLE-LTEV-CFB is rated max 25VDC input. Maximum Loop Current: 1.2mA End of Line Resistor (EOLR) Value: 10K (2 req'd)Electrical Ratings for 3 PGM Outputs: Open Collector Outputs: Maximum Voltage 3V whenactive; 15V maximum when not active. Note: ModelSLE-LTEV-CFB is rated max 25VDC output. Maximum PGM Sink Current: 50mA (up to 15VDC),25mA (15.1VDC - 25VDC)Physical (W x H x D) Metal Housing: 11½ x 9½ x 3½" (29.2 x 24.1 x 8.9cm) Mounting: Metal housing includes two keyhole slots forwall mounting (see measurements on page 7)Environmental Operating Temperature: 0°C - 49°C (32°F - 120°F) Humidity: Maximum 93% Non-Condensing Indoor / dry location use only*For Commercial Fire installations, a UL Listed Fire Alarm regulated power supply or FACP regulated auxiliary output is required.