INSTRUCTIONS1. Run the wire to be monitored throughaperture.2. Mount the sensor.3. Connect output wiring.A. Use up to 14 AWG copper wires.B. Ensure load matches the output shown onthe sensor label.4. Adjust SetpointA. Use the potentiometer to adjust the set-point.AS1 DODC SERIESAC Current Operated SwitchWith Dual OutputAS1 - DODC - FLCASE STYLE:FL - Fixed Core, Top TerminalsOUTPUT (Solid State Switch) :DODC - Dual Normally Open, 1.0A @ 30VDCSENSOR TYPE:AS1 - AC current operated switch with single range0.75A -- 20AAS2 - AC current operated switch with single range20A -- 50AModel Number KeySpecifi cationsPower Required None - self poweredOutput Switch Isolated Solid State SwitchSwitch Rating DODC - N.O. 1A @ 30VDCOff State Leakage <10 MicroampsResponse Time 100 mSHysteresis < 8% of SetpointSet Point Ranges A Contact: Adjustable 0.75A - 20AB Contact: Adjustable 0.75A - 20AStart-up Delay 2.0 Seconds (fixed)Setpoint Adjust 4 Turn potentiometerIsolation Voltage Designed to meet UL508 require-ments to 1,270 VACTested to 5,000 VACFrequency Range 6-100HzSensing Apeture -FL 0.75” (19mm)Environmental -4 to122Deg F (-20 to 50 Deg C)0-95% RH, Non CondensingRanges & Maximum AmpsQuick “How To” GuideAS1-DODC-FL Inst. Rev 2 12/14 P/N 39-360-00013511 Charter Park Drive, San Jose, CA 95136800-959-4014 or +1-408-871-7510 Phone+1-408-871-7515 FAXsales@nktechnologies.com, www.nktechnologies.comKnow Your PowerOther NK Technologies Products Include:AC & DC Current TransducersAC & DC Current Operated Switches1φ & 3φPower TransducersCurrent & Potential Transformers (CTs&PTs)TYPE RANGE MAXIMUM INPUT AMPSFIXED CORE 0.75- 20 ACONTINUOUS 6 SEC. 1 SEC.50A 200A 400AFIXED CORE 20-50 A 50A 200A 400A