INSTRUCTIONS1. Run the wire you are monitoring through ap-erture.2. Mount the sensor.3. Connect power & output wiring.A. Make sure power supply matches specifications.B. Make sure output load matches the output shownon the sensors’ label.4. Adjust SetpointA. Chose correct range by positioning the RangeJumperB. Use the potentiometer to adjust the setpoint.DS3 SERIESDC Current Operated SwitchDS3 - SDT - 24UPower Supply24U 24VAC/DC12U 12VAC/DCOUTPUT:NOU Normally Open Solid State Switch, 0.15A@ 240 VAC/VDCSDT Single Pole Double Throw (SPDT orForm C) relaySENSOR TYPE:DS3 DC current sensing switch with 3 jumper selectablerange and adjustable setpointModel Number KeySpecifi cationsPower 24U =15-28 VAC/DC12U =11.4-20 VAC/DCConsumption Relay (SDT) <20mA de-energized<133mA energizedSolid State <20mA de-energized<90mA energizedSetpoint Ranges (DC) 2-20A, 10-50A, 20-100A(AC) 2-17, 10-41, 20-80ASetpoint Adjust 11 Turn potentiometerIsolation Voltage 3KVFrequency Range DC to 400 HzRepeatability 0.5%Hysteresis 5% of setpointSensing Aperture 0.75” (19mm)Case UL 94-V0 Flammability RatedOutput Rating & EnvironmentalNOU Isolated Solid State Switch0.15A @ 240 VAC/DCOff State Leakage NONEOperating Temp. -20 to 50°C(-4 to 122°F)Storage Temp. -30 to 60°C (-22 to 140°F)0-95% RH, Non CondensingSDT SPDT (Form C) Relay5A General Purpose @ 240 VAC5A @ 30 VDCOperating and Storage -20 to 50°C (-4 to 122°F)0-95% RH, Non CondensingApprovals UL/cUL, CERanges & Maximum AmpsRANGESOLID CORE2-20 A10-50 A20-100 ARANGEJUMPERLOWMIDHIGHMAXCONTINUOUSNo limitMAX5 SEC.No limitQuick “How To” GuideDS3 Inst. Rev13, 08/18 P/N 39300010380 ms max60 ms max60 ms max60 ms maxALL RangesON Delay5% over Setpoint50% over Setpoint100% over SetpointOFF DelaySwitching Response Time3511 Charter Park Drive, San Jose, CA 95136800-959-4014 or +1-408-871-7510 Phone+1-408-871-7515 FAXsales@nktechnologies.com, www.nktechnologies.comWarning! Risk of DangerSafe operation can only be guaranteed if thecurrent switch is used for the purpose it hasbeen designed for and within the limits of thetechnical specification. When this symbol isused, it means you must consult all documen-tation to understand the nature of potentialhazards and the action required to avoid them.Warning! Risk of ShockWhen operating the current switch, certainparts of the module may carry hazardous livevoltage (e.g. primary conductor, controlledload). The switch should not be put into op-eration if the installation is not complete.For products intended for the EU market, the following isapplicable to the CE compliance of the product:The DS3 series comply with EN 61010-1 CAT III 300Vrmsmax. line-to-neutral measurement category. If insulated cable isused for the primary circuit, the voltage rating of the measure-ment category can be improved according to the insulationcharacteristics given by the cable manufacturer.