INSTRUCTIONS1. Run the wire you are monitoring through aper-ture.2. Mount the sensor to a surface if needed.3. Connect output wiring.A. Use up to 14 AWG 75/90˚ C copper wires.B. Make sure output load does not exceed productspecifications.C. Connect 24 VDC power supply and load inseries.4. Select RangeA. Chose correct range by positioning the Rangeswitch.AT & ATR 2, 3 & 4 SERIESAC Current Transducers4-20mA OutputTrue RMS or Average RespondingAT R 3 - 420 - 24L - FLOUTPUT:420 - 4-20mARANGE2 - 100, 133, 200 A3 - 375, 500, 750 A4 - 1000, 1333, 2000 ASENSOR TYPE:AT - AC current sensor, 4-20 mA outputloop poweredModel Number KeySpecificationsPower SupplyQuick “How To” GuideCASE STYLEFL- Fixed coreCurrent Ranges Field Selectable from 0-2000ACurrent Measurement range 0-2000A@600V, CAT IIIOutput Signal 4-20mA, Loop PoweredOutput Limit 23 mAPower Supply 24VDC nominal, 40VDC max.Overvoltage Cat. I, Class 2 or power limitedpower supplyAccuracy 1.0% FSMeasurement True RMS or Average RespondingFrequency Range ATR: 10-400 HzAT: 50-60 Hz, SinusoidalIsolation Voltage 3kVResponse Time 500 ms (to 90% of step change)Environmental -4 to 122°F (-20 to 50°C) operating ambienttemperature.0-95%RH, non-condensingPollution Degree 2Altitude to 2000 metersCase UL 94V-0 Flammability rated thermoplasticListing UL and cUL ListedCE CertifiedRoHS CompliantMinimum Power Supply = 12 VDC + Total Loop Voltage Drop0 250 500 750 100032V22V12VOperatingRangeTotal Loop Impedance (Ohms)LOOPPOWER(VDC)POWER SUPPLY:24L- 24VDC Loop PoweredMeasurementR - True RMS(Blank) - Average Responding3511 Charter Park Drive, San Jose, CA 95136Phone: 800-959-4014 or 408-871-7510Fax: 408-871-7515sales@nktechnologies.com, www.nktechnologies.com AT/ATR 2/3/4 Series 292001301-3Know Your PowerOther NK Technologies Products Include:AC & DC Current TransducersAC & DC Current Operated Switches1φ & 3φPower TransducersCurrent & Potential Transformers (CTs&PTs)Caution! Risk of electric shock or per-sonal injurySafe operation can only be guaranteed if thetransducer is used for the purpose for whichit was designed and within the limits of thetechnical specifications. When this symbolis used, it means you should consult alldocumentation to understand the nature ofpotential hazards and the action required toavoid them.Caution! Risk of hazardous voltageWhen operating the transducer, certain partsmay carry hazardous live voltage (e. g. pri-mary conductor, secondary terminals). Thetransducer should not be put into service ifthe installation is not complete.