INSTRUCTIONS1. Run the wire you are monitoring through aper-ture.2. Mount the sensor to a surface if needed.3. Connect output wiring.A. Use up to 14AWG copper wires.B. 0-5/10 VDC Models: Make sure output loadis at least 100 KΩ to achieve stated accuracy4. Chose correct range by positioning the RangeJumper.5. Energize the sensor by connecting 24 VDC to thepower supply terminals.ATP R 1 - 010 - 24D - SPOUTPUT:005- 0-5VDC010- 0-10VDCRANGE0 - 2 & 5 Amps1 - 10, 20 or 50 Amps2 - 100, 150 or 200 AmpsSENSOR TYPE:ATPR - True RMS AC current transducers, 24VDCpowered 0-5 or 10VDC output.Model Number KeySpecifi cationsQuick “How To” GuideCASE STYLESP- Split CoreOutput Signal 0-5VDC or 0-10VDC proportional tothe RMS CurrentOutput Limit 112% of standard output rangemaximum valueFrequency Range 10-400 HzResponse Time( 90% of step change) 600mSAccuracy 1.0% Full Scale Split CoreLoading 100K Ω MinimumPower Supply 24VDCSee “Output Wiring” section.Isolation Voltage UL listed to 1,270VAC, tested to5kVCase UL 94V-0 Flammability ratedthermoplasticEnvironmental -20 to 50 Deg. C, (-4-122 Deg F)0-95% RH, non-condensingListing Designed to meet CE, UL 508Industrial Control EquipmentInput MaximumsATPR0 0-2A 125 250ATPR0 0-5A 125 250ATPR1 0-10A 125 250ATPR1 0-20A 150 300ATPR1 0-50A 215 400ATPR2 0-100A 300 600ATPR2 0-150A 450 800ATPR2 0-200A 500 1,000MAXIMUM INPUT AMPSMODEL RANGE 6 SEC. 1 SEC.POWER SUPPLY:24D- 24VDC with non-isolated output3511 Charter Park Drive, San Jose CA 95136800-959-4014 or +1-408-871-7510 Phone+1-408-871-7515 FAXsales@nktechnologies.com, www.nktechnologies.comKnow Your PowerOther NK Technologies Products Include:AC & DC Current TransducersAC & DC Current Operated Switches1φ & 3φPower TransducersCurrent & Potential Transformers (CTs&PTs)ATPR Inst. Rev 1, 10/12 P/N 292000503ATPR SERIESPowered RMS AC Current Transducers0-200A Input Maximum Range0-5VDC or 0-10VDC Output