2ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANEThe Trinity boiler is set to operate with Natural Gas; LP Conversion Kit Part No. 82650-1 for Ti100’s, Ti150’s andTi200’s, or LP Conversion Kit Part No. 83017-1 for Ti400’s is included with each boiler and must be installed beforeoperating with Propane.Liquefied Petroleum (LP) propane gas is heavier than air; it is imperative that your boiler is not installed in a pit orsimilar location that will permit heavier than air gas to collect. Local Codes may require appliances fueled with LP gasbe provided with an approved means, of removing unburned gases from the room. Check your local codes for thisrequirement.WarningTHIS BOILER MUST HAVE WATERFLOWING THROUGH IT WHENEVERTHE BURNER IS ON. FAILURE TO DOTHIS WILL DAMAGE THE UNIT ANDVOID THE WARRANTY.01002003004000-20003000 4000 5000 6000 7000 8000 9000 10000Elevation (ft)Input (Mbh)Ti150 Ti200 Ti400 Ti1001.0 SPECIFICATIONSDescription Ti 100 Ti 150 Ti 200 Ti 400Input (BTUx1000)Input Capacity - Max. / Min.Natural =100 / 15Propane= 100 / 15Natural =150 / 25Propane= 145 / 25Natural = 200 / 25Propane= 194 / 25Natural = 399 / 75Propane= 399 / 75Output (BTUx1000)Output Capacity - Max./ Min.Natural =92.7 / 13.9Propane = 92.7/ 13.9Natural =139 / 23.2Propane = 134 / 23.2Natural = 185 / 23.2Propane = 180 / 23.2Natural = 370 / 69.5Propane = 370 / 69.5Steady State Efficiency 95% 95% 94% 94%AFUE Efficiency 95.1%Venting material CPVC, PVC (See Section 3.1)Max. Vent lengths Natural Gas 3” @ 105’ EquivalentMax. Vent lengths Propane 3” @ 105’ Equivalent 3” @ 50’ Equivalent4” @ 30’ Equivalent6” @ 65’ EquivalentWeight 80 lbs. 80 lbs. 110 lbs. 205 lbs.Dimensions L-W-D (Inches) 22.5x15.25x14 22.5x15.25x14 22.5x15.25x17.25 23.5x21x36Clearance to Combustibles 0”1.1 High Altitude OperationThe Trinity boiler is designed to operate to capacity ininstallations with 2000 feet of elevation or less. Aselevations higher than 2000 feet have less dense air, the unitis not capable of providing its specified capacity. (SeeChart).In Canada:De-rate by 5% for altitudes between 2000 and 4500 feet.For altitudes above 4500 feet consult with local authorities.In USA:De-rate by 4% for every 1000 feet over 2000 feet.CAUTION At elevations greater than 2000 feet, thecombustion of the Trinity must be checked with a calibratedcombustion tester to ensure safe and reliable operation.Consult Section 5.20 for instructions on adjusting the input toprovide proper operation. It is the Installers responsibility tocheck the combustion, and to adjust the combustion inaccordance to Section 5.22.0 INSTALLATION REQUIREMENTSImportant: Carbon Monoxide DetectorsThe installation of your NY Thermal Trinity gas boiler mustconform to the requirements of your local authority, and the National Fuel Gas Code ANSI Z223.1 and or CAN/CGA B149 InstallationCodes. Where required by the Authority, the installation must conform to the standard for “Controls and Safety Devices for AutomaticallyFired Boilers ANSI/ASME CSD-1.