Opening and Closing the DoorCaution Disconnect external power to the MON-10467 (AC) and use the externalcircuit breaker box to completely remove mains power before opening the device forservice.Attention Débranchez l'alimentation externe du MON-10467 (AC) et utilisez leboîtier de disjoncteur externe pour couper complètement l'alimentation secteur avantd'ouvrir l'appareil pour l'entretien.Caution Remove power to the MON-10467 (DC) before opening it for service.Attention Mettez le MON-10467 (DC) hors tension avant de l'ouvrir pourl'entretien.Notice Do not put a load on the device door while it is open.Complete the following steps to open and close the door of the MON-10467.1. Loosen the four captive screws on the door of the device with a 1/4 in. socket or 6 mm(1/4 in.) flat-blade screwdriver.2. Open the door of the device slowly.3. Clean the gasket and gasket mating surface with a dry or damp cloth prior to closing thedevice door.4. Close the door slowly.5. Tighten the four captive screws on the door of the device to 1.3 N · m (11.5 lb · in.).MountingThe MON-10467 must be mounted upright to a rigid surface such as a wall, panel, strutchannel, or metal post. For installations that may experience vibration, NI recommends using athread locking compound or lock nuts.Each flange has several bolt locations as shown in the following figure. The flanges are 4 mm(0.157 in.) thick. The V-notch on the rear facilitates mounting to a round surface such as a pipeor pole using a pipe clamp bracket.MON-10467 User Guide | © National Instruments | 13