1200XX/120X-IMXX Models Refrigerator Service ManualAngled bafflesrequired whenthe roof exhaustvent is inboardof the condenserAngle mustnot exceed45 degreesBaffles requiredwhen openingbetween outsidewall and coolingunit is over 1 inchIntake ventRoof ventCondenser1/4 inchor lessIntake ventAbsorber coilsRoof exhaust ventCondenserTop baffle requiredwhen the clearancefrom the undersideof the roof to thetop of the refrigeratorexceeds 1/4 inch.Fans (2)Side wall bafflesrequired when theclearance between theenclosure side wallsand refrigeratorexceeds 1/8 inchBafflesThe minimum and maximum clearances for installingthe refrigerator or correcting ventilation problems onroof vented units are listed in Table 1 below. Bafflesare required whenever installations exceed maximumclearances listed in Table 1. Figure 10 and Figure 11show baffle locations.Vertical Angled BafflesVertical angled baffles are required when the roofexhaust vent is installed inboard of the condenser.Figure 12 shows the angled vertical baffles requiredon inboard roof vent installations. The horizontal wallbaffles are required whenever the distance between thecooling unit and the interior surface of the outside wallexceeds one inch.Figure 10. Back view–roof exhaust ventingFigure 11. Baffles required for an inboardroof exhaust vent installationMinimum MaximumBottom 0 inch 0 inchSides (each) 0 inch 1/8 inchTop 0 inch 1/4 inchRear 0 inch 1 inchTable 1. Clearances for roof vented installations20