59G(1 1/4"-2")Unit 6 Unit 2 Unit 1System ControllerStorage tank supply line(1 1/4"-2")Storage tank return line(Copper or Stainless Pipe)(Copper or Stainless Pipe)Storage Tank Circulation Pump 1Storage Tank Circulation Pump 2(if Necessary)Gas PipeHot WaterStorage TankRelief ValveHot water supply line(Copper or Stainless Pipe)Return linecirculation pumpHot water return line(Copper or Stainless Pipe)Cold Water Supply* Size the water supply piping toallow for maximum flow ratesof the building.* Set dipswitch 3 to OFF.(See SC-201-6M Installation Manualpage 13)* If the tank thermostat will control the pumpset dipswitch 2 to OFF.(See SC-201-6M Installation Manual)Do not connect more than one pump to thetank thermostat.Hot WaterSupplyRemoteControllerOption 2-UnitControlOption 1-TankThermostat ControlWhen installing 2 pumps in parallelThe system controller will stop the units from heating when the tank is up to temperature,and the unit will cut the flow through it to 1.3 GPM.Install the plumbing so that a change in flow will not damage the pump.ThermostatSystem select connectorConnect to the “Sto-rage system”connector"Pump ControlWires (useexternal relay)* Alsodisconnect thisconnector on units 2-6Disconnect this ConnectorB-2. Example of Installation with a Storage Tank and Recirculation SystemThe pump will push water through the Multi-System to heat up the tank.When the return temperature is high, the flow within the device will be limited to 1.3 GPM*.* For the set temperature of the remote control, use the temperature (of the thermostat) + about 9°F.* To achieve the highest recovery, size the storage tank circulation pump for maximum capacity.( N-132M: 12 GPM (each) @ 50 ft. of head (160°F setting or less), N-084M: 7.4 GPM (each) @ 40 ft. of head(160°F setting or less) + piping losses through the system). Verify the supply pressure to the units is at least 30 PSI.