62 AFP-200 Instruction PN 15511:F2 10/11/994.6 Supervisory OperationSupervisory operation is similar to alarm operation, but with the following differences:• The piezo sounds a warbling tone.• The Supervisory LED flashes.• The LCD display status banner is ACTIVE.• Silenced alarms do not resound.• Timers do not start• The Supervisory relay activates.• The Alarm relay does not activate.A typical supervisory event display is shown in thescreen to the right.Note that, like alarms, supervisory signals latch andmay have their own Control-by-Event. They do notcause resound of alarms or reactivation of silencedalarm CBE. Supervisory circuits may also opencircuit troubles, which operate like any other trouble.If the event is a security point activation, this LED will operate the same as a supervisory, but the LCD displaywill show the security type code. Refer to Appendix E for further information on security alarms.4.7 Non-Alarm Point OperationNon-alarm points are MMX modules that activate CBE but do not activate the System Alarm LED or the piezosounder. These points are tracking and have three type codes:• Non fire codes send a message to the LCD, history file, printer, or LCD-80, except when the system is inalarm. They are generally used for energy management or other non-fire situations.• Hazard Alert codes send a message to the LCD, history file, printer, and LCD-80 (status is ACTIVE), andactivate the four Notification Appliance Circuits steadily, regardless of the coding selection in Zone 98. Thesepoints may be used for monitoring critical processes or other hazardous situations, such as a tornado.• Fire Control codes send messages to the LCD, history file, printer and LCD-80, regardless of the state of thecontrol panel. These codes are generally used for air handler shutdown and are intended to override automaticfire functions.4.8 Trouble Monitor Point OperationTrouble monitor-type MMX modules monitor remote power supplies or other external equipment. Operation issimilar to trouble operation but with the following differences:• The display status banner is ACTIVE.• The type code is TROUBLE MON.• The modules latch.• The modules may have control-by-event.A C T I V E @ T A M P E RS P R I N K L E R @ V A L V E @ 1 0 5F L R @ 5 @ M A I N @ B U I L D I N G1 1 : 1 3 A @ 1 2 / 2 5 / 9 7 @ M 3 7