Special Function Screens 2. Program ChangeAFP-300/AFP-400 Programming PN 50259:C1 06/19/97 17R0-R9 (ReleasingFunctions)The Releasing Function screen provides fields for changing the delay time or PAS.From the Special Function Change screen, select a function (R0-R9) to display theReleasing Function screen:Figure 23 Releasing Function ScreenF5-F6 (Time ControlFunctions)The Time Control screen provides fields for changing the start time, stop time, or daysof the week. From the Special Function Change screen, select F5 or F6 to display theTime Control screen:Figure 24 Time Control ScreenF7 (Holiday) The Holiday screen provides fields for specifying up to nine holiday dates. From theSpecial Function Change screen, select F7 to display the Holiday screen:Figure 25 Holiday ScreenF8 (Code Type) The Code Type screen provides fields for specifying one of four code types: MarchTime, Temporal, California, or Two Stage. From the Special Function Change screen,select F8 to display the Code Type screen:Figure 26 Code Type ScreenF9 (Pre-Alarm) The Pre-Alarm screen provides fields for programming the Alert and Action Pre-Alarmfunctions. From the Special Function Change screen, select F9 to display the Pre-Alarmscreen:Figure 27 Pre-Alarm ScreenPRG RELEASE FUNCTION RELEASE CONTROLDELAY=00 ABORT=ULI CROSS=N SOAK=0000 R00PRG TIME FUNCTION TIME CONTROLON=**:** OFF=**:** DAYS=******** F05PRG HOLIDAY FUNC **/** **/** **/****/** **/** **/** **/** **/** **/**PRG CODING FUNCTION CODE TYPEMARCH TIME F08Code Type (Refer to “NAC Coding” on page 32)PRG PRELARM FUNCT ALERTF09Action or Alert (Refer to “Selecting a Pre-Alarm Level” on page 38)www.PDF-Zoo.com