26 NFS2-640/E Operations Manual — P/N 52743:F1 06/16/2011Operation of the Control Panel Disabled Points Mode of Operation3.8 Disabled Points Mode of OperationThe control panel indicates disabled points by displaying a screen for each disabled detector,monitor module, and control/relay module. Disabled points do not cause an alarm or anyControl-by-Event activity. If more than one point is disabled, the control panel displays by priority,mimicking the alarms.When one or more points are disabled, the control panel does the following:• Holds all disabled output points in the off-state• Flashes the SYSTEM TROUBLE LED• Lights the POINT DISABLED LED• Sends a Disabled Point message to the LCD display, History buffer and installed printers,FDU-80 annunciators, and CRT-2s• Displays a message for each disabled pointFigure 3.10 Sample Disabled Point Message3.9 Non-Alarm Mode of Operation3.9.1 Purpose of Non-Alarm PointsNon-Alarm points are addressable monitor modules programmed with one of the Non-Alarm TypeCodes listed in Table 3.4. Non-Alarm points, except Non-Fire, operate like monitored systemfunctions that can produce troubles—but with the differences shown in the following sections.! CAUTION:Disabling a zone disables all input and output devices associated with the zone.Disable messageType Code of the disabled deviceAddress of thedisabled deviceD I S A B L T A M P E R I N T E N S I V E C A R E U N I TE A S T E R N W I N G 0 3 : 2 0 P 0 4 1 5 0 8 1 M 1 5 9Custom descriptor forthis device locationTime and date of troubleExtended 12 charactercustom labelMonitor ModulesType Code Latching(Y/N) Purpose What it doesACCESS MONTR N Used for monitoring building access Activates CBEACK SWITCH N Performs Acknowledge function Silences panel sounder, gives anAcknowledge message on the panel LCDALLCALL PAGE N Activates all speaker circuits for paging Activates speakersDRILL SWITCH N Performs Drill function Activates silenceable outputsFIRE CONTROL N Used for air handler shutdown, intended to overridenormal operating automatic functionsActivates CBE, does NOT light anindicator at the control panelNON-FIRE N Used for energy management or other non-firesituations. Does not affect operation of the control panelActivates CBE, does NOT light anindicator at the control panelPAS INHIBIT N Inhibits Positive Alarm Sequence Inhibits Positive Alarm SequenceRESET SWITCH N Performs Reset function Resets control panelSIL SWITCH N Performs Signal Silence function Turns off all activated silenceable outputsTELE PAGE N Performs function of Page Button on FFT-7 Allows remote paging to a fire areaABORT SWITCH N Indicates Active at the panel Aborts activation of a releasing zoneTable 3.4 Non-Alarm Type Codes