9E. 04.99• G.13.11.02FunctionCompact gas unitThe compact gas units for Nu-Way gas burners are preassembled and checked for leaks.Version KE 15:1-stage precision pressure regulator with high controlquality and adjustable starting gas pressure.Version KE 10:1-stage precision pressure controller with high controlquality and adjustable start gas pressure.The compact gas unit KE 10 is provided with a non-ad-justable gas pressure switch (switching point 12 mbarfalling).Technical data of compact gas unitGas types: Natural gas, propane and butane, acc. to DIN EN 437/DIN EN 88Inlet pressure: max. 360 (KE 15), max. 70 mbar (KE 10)min. 18 mbarMax. pressure drop: 50 mbar (supply pressure - output pressure)Ambient temperature: -10 °C to +60 °CConnecting flanges: The connecting flanges are secured with 4 screws. The flanges can beturned through 90° or 180° in each case. Pressure measuring points ininlet and in outlet.Filter: Nylon wire gauze with chopped-strands mat fleeceSolenoid valves (T. A):Closing time: < 1 sSwitching frequency:anyDuty factor: 100% DFDegree of protection:IP 54 to IEC 529Adjustable gas pressure switch(only on version KE 15)The gas pressure monitor serves to monitor the gas in-let pressure. The burner is shut down if the gas inletpressure drops below the set minimum value (presetat factory to 12 mbar). The burner starts up automati-cally when the minimum pressure is exceeded.This setting should be retained.P w