INSTALLATION | Specification62 www.ochsner.com | 982000-AIR-M2-M4-EN03.114.2 Heat pumps for single phase alternatingcurrent14.2.1 Data tableAIR 11 C11B AIR 18 C11BINDOOR UNIT:Hydraulic variant M2-1/M2-2/M2-3/M2-4 M2-1/M2-2/M2-3/M2-4Dimensions HxWxD [mm] 1286x600x680 1286x600x680Hydraulic connection DN 32 (1 1/4”) male DN 32 (1 1/4”) maleWeight [kg] 124 135Casing colour Tiger white 29/11289/grey RAL7016Tiger white 29/11289/grey RAL7016HEATING MODE PERFORMANCE DATA:Standard point L10/W35Heating output [kW] 11.1 16.1Total power consumption / operating current [kW]/[A] 2.5 / 12.9 3.4 / 20.8Coefficient of performance EN 14511/EN 255 4.4 / 4.7 4.8 / 5Operating point L7/W35Heating output [kW] 10.2 14.8Total power consumption / operating current [kW]/[A] 2.4 / 12.4 3.3 / 20.5Coefficient of performance EN 14511/EN 255 4.3 / 4.5 4.5 / 4.8Standard point A2/W35Heating output [kW] 8.9 13Total power consumption / operating current [kW]/[A] 2.3 / 11.6 3.2 / 19.9Coefficient of performance EN 14511/EN 255 4 / 4.2 4 / 4.3Standard point L-7/W35Heating output [kW] 6.9 10.1Total power consumption / operating current [kW]/[A] 2.2 / 11.5 3.2 / 19.9Coefficient of performance EN 14511/EN 255 3.1 / 3.3 3.1 / 3.3Operating point L-10/W35Heating output [kW] 6.3 9.2Total power consumption / operating current [kW]/[A] 2.1 / 10.9 3.1 / 19.5Coefficient of performance EN 14511/EN 255 3 / 3.3 2.9 / 3.1Operating point A2/W50Heating output kW 8.5 12.3Total power consumption / operating current [kW]/[A] 3 / 15.5 4.3 / 26.1Coefficient of performance EN 14511/EN 255 2.8 / 2.9 2.9 / 3.1Operating point A2/W60Heating output [kW] 8.4 11.5Total power consumption / operating current [kW]/[A] 3.3 / 17.1 4.5 / 27.4Coefficient of performance EN 14511/EN 255 2.5 / 2.6 2.6 / 2.8COOLING MODE PERFORMANCE DATA:Operating point A30/W18Cooling capacity [kW] 9.5 9.9Total power consumption / operating current [kW]/[A] 3.2 / 16.6 3.4 / 21.1Energy efficiency ratio EER 3 2.9Operating point A30/W7Cooling capacity [kW] 8.6 9.3Total power consumption / operating current [kW]/[A] 3.1 / 16 3.4 / 21.1Energy efficiency ratio EER 2.8 2.7SPECIFICATION:Phases/nominal voltage/frequency [~]/[V]/[Hz] 1/230/50 1/230/50Output factor cos ϕ 0.84 0.71Fuse C25A C40AMax. operating current [A] 20.8 30Max. starting current/max. with soft start [A] 97 / 48.5 160/80Sound power level/sound pressure level (at 1 m distance) [dBA] 44.5 / 36.5 47.5 / 39.5