English 109. WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER9-1 HOW TO CONNECT WIRINGS• Remove the electric parts box cover and connect the wiring.NOTES• Remote controller wiring and crossover wiring should be runat least 50 mm from the power cable. if too close, malfunctioncould result from electronic noise (noise from outside).• For remote control wiring, see “Remote Controller InstallationInstructions.”• For electric wiring, also see “Electric Wiring Schematic Dia-gram” label.• Be sure not to connect the power cable to the terminal block(for remote controller and crossover wiring). Doing so coulddamage the entire system.• Remote controller cord, crossover wiringDo not confuse the two when connecting to the terminal block(for remote controller and crossover wiring).• Fasten the wiring with accessory clamp (6).• If mounting a remote controller on the unit, wire as shown inthe figure on the right.• If wiring from the piping side, wire as shown in the figure on the right.CAUTION• When cramping wiring, use the included cramping material to do an appropriate cramp to prevent unduepressure on the wiring connections. When carrying out the wiring, bundle the wires to prevent the switchbox lid from lifting, and attach the lid firmly. When attaching the switch box avoid getting wires caught alwaysuse a wiring through-lid to prevent damage to the wires.• Make sure to avoid external force to the field wiring(∗) such as by laying them in protection pipes or in thewall.Electric parts boxClamp fastenerConnectingwire (∗)Clamp(accessory)Cut off excess afterfastening.Wiring betweenunits (∗)Remote controller wire (∗)Connecting wire (∗)Pass through hole ofremote controllerfastening plate.Pass through holeof opposite framepanel in samemanner.Wiring between units (∗) Connecting wiring (∗)Remote controllerwire (∗)Electric parts boxFasten with accessory clamp (6).Crossover wiringRemote controller wiringElectric wiring