15.2. PERFORMANCE DATACS-A18BD3P/CU-A18BBP5, CS-C18BD3P/CU-C18BBP5ModelCOOLING PERFORMANCEAmbient Temperature Air Entering Condenser (°C D.B.)Return 25°C 30°C 35°C 40°C 45°CAir TC SHC IPT TC SHC IPT TC SHC IPT TC SHC IPT TC SHC IPTD.B. W.B. kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW17 6.84 5.98 2.09 6.58 5.88 2.25 6.25 5.76 2.39 5.86 5.51 2.55 5.40 5.07 2.6823 19 7.17 5.19 2.25 6.91 5.13 2.39 6.58 5.01 2.55 6.25 4.88 2.71 5.86 4.68 2.8322 7.76 4.02 2.49 7.50 4.02 2.62 7.17 3.98 2.78 6.84 3.93 2.91 6.44 3.82 3.0617 6.80 5.95 2.09 6.54 5.84 2.25 6.21 5.72 2.39 5.82 5.47 2.55 5.36 5.04 2.6825 19 7.12 5.16 2.25 6.86 5.10 2.39 6.54 4.98 2.55 6.21 4.85 2.71 5.82 4.65 2.8322 7.72 3.99 2.49 7.46 4.00 2.62 7.12 3.95 2.78 6.80 3.90 2.91 6.41 3.80 3.0617 6.76 5.91 2.09 6.50 5.81 2.25 6.18 5.69 2.39 5.79 5.44 2.55 5.33 5.01 2.6827 19 7.09 5.13 2.25 6.83 5.07 2.39 6.50 4.95 2.55 6.18 4.82 2.71 5.79 4.63 2.8322 7.67 3.96 2.49 7.41 3.97 2.62 7.09 3.93 2.78 6.76 3.88 2.91 6.37 3.77 3.0617 6.72 5.88 2.09 6.46 5.78 2.25 6.15 5.66 2.39 5.76 5.41 2.55 5.30 4.98 2.6829 19 7.05 5.10 2.25 6.79 5.05 2.39 6.46 4.92 2.55 6.15 4.79 2.71 5.76 4.60 2.8322 7.63 3.95 2.49 7.37 3.95 2.62 7.05 3.91 2.78 6.72 3.86 2.91 6.33 3.75 3.0617 6.67 5.83 2.09 6.42 5.73 2.25 6.09 5.61 2.39 5.71 5.37 2.55 5.26 4.94 2.6832 19 6.99 5.06 2.25 6.73 5.00 2.39 6.42 4.89 2.55 6.09 4.76 2.71 5.71 4.57 2.8322 7.57 3.91 2.49 7.32 3.92 2.62 6.99 3.88 2.78 6.67 3.82 2.91 6.29 3.73 3.06Legend : BF Bypass Factor 0.20 SHC Sensible Heat Capacity TC Total Cooling CapacityCAPACITY SELECTION NOTES(1) The table above is based on unit nominal evaporator airflow,correction factor must therefore be applied for selectionsaway from this condition.COOLING CORRECTION FACTORSEVAP. AIR FLOW m 3 / min (l/s) 14 (233) 17 (283) 20 (333) 23 (383)SHC Sensible Heat Capacity 0.86 0.93 1 1.08TC Total Cooling Capacity 0.92 0.96 1 1.0534