8.4. Automatic Operation• Automatic operation can be set using remote control.• This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature.• After judged the temperature, the operation mode is determined by refering to the below standard.• Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the settingtemperature as shown in below table.• Operation mode will be determine again for judgement after 1 hour of operation, if the room temperature reaches to settemperature and compressor off time is over 7 minutes 30 seconds continuously.The present mode will be continued, if the room temperature does not reach to set temperature (Compressor keeps running) eventhrough after1 hour from automatic operation mode started.Present Judgement Next ModeMode Cooling Soft Dry HeatingO OCooling 23∞C Cooling (Judgement: Not Applicable (Judgement:Heating 23∞C & Above) Below 23∞C)O OSoft Dry 20∞C Soft Dry Not Applicable (Judgement: (Judgement:Heating 20∞C & Above) Below 20∞C)O OHeating Cooling (Judgement: Not Applicable (Judgement:25∞C Heating 25∞C & Above) Below 25∞C)• Automatic Set TemperatureFor each operation, set temperature will automaticlly set as shown below.• The setting temperature for all the operations can be changed one level up or one level down from the standard temperatureas shown in below table by pressing on the temperature up or temperature down button at remote control.Operation Hi (Standard) Lo(+2∞C) (±0∞C) (-2∞C)Cooling 27∞C 25∞C 23∞CSoft Dry 24∞C 22∞C 20∞CHeating 23∞C 21∞C 19∞C• The operation mode judging temperature and standard setting temperature can be increased by 2∞C permanently, by open thecircuit of JX1 at indoor electronic controller.18CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD