7415.1.1 Relationship between the condition of the air conditioner and pressure andelectric currentCooling ModeCondition of theair conditioner Low Pressure High Pressure Electric current during operationInsufficient refrigerant(gas leakage) Ô Ô ÔClogged capillary tube orstrainer Ô Ô ÔShort circuit in the indoor unit Ô Ô ÔHeat radiation deficiencyof the outdoor unit Ò Ò ÒInefficient compression Ò Ô Ô• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.15.1.2 Diagnosis methods of a malfunction of a compressorNature of fault SymptomInsufficient compressing of a compressor• Electric current during operation becomes approximately 20% lower than the normal value.• The discharge tube of the compressor becomes abnormally hot (normally 70°C to 90°C).• The different between high pressure and low pressure becomes almost zero.Locked compressor• Electric current reaches a high level abnormally, and the value exceeds the limit of anammeter. In some cases, a breaker turns off.• The compressor has a humming sound.