4415.4. Error Codes TableNote:“O” - Frequency measured and fan speed fixed.The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heardfollowing by pressing the “CHECK” button at Remote Control.Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to ErrorCodes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound ischanged from one “beep” to four “beep” sounds.Abnormality / Protection control AbnormalityJudgementEmergencyoperation Primary location to verifyDiagnosisdisplayH00 No abnormality detected — Normal operation —H11 Indoor / outdoor abnormalcommunication> 1 min. after startingoperationIndoor fan operationonly• Internal / external cable connections• Indoor / Outdoor PCBH14 Indoor intake air temperature sensorabnormalityContinue for 5 sec. — • Intake air temperature sensor(defective or disconnected)H15 Outdoor compressor temperature sensorabnormalityContinue for 5 sec. — • Compressor temperature sensor(defective or disconnected)H16 Outdoor Current Transformer opencircuit— — • Outdoor PCB• IPM (Power transistor) moduleH19 Indoor fan motor merchanism lock — — • Indoor PCB• Fan motorH23 Indoor heat exchanger temperaturesensor abnormalityContinue for 5 sec. O(Cooling only)• Heat exchanger temperature sensor(defective or disconnected)H24 Indoor heat exchanger temperaturesensor 2 abnormalityContinue for 5 sec. — • Heat exchanger temperature sensor 2(defective or disconnected)H26 Ion abnormality — — • Indoor PCB• IonH27 Outdoor air temperature sensorabnormalityContinue for 5 sec. O • Outdoor temperature sensor (defectiveor disconnected)H28 Outdoor heat exchanger temperaturesensor abnormalityContinue for 5 sec. O • Outdoor heat exchanger temperaturesensor (defective or disconnected)H30 Discharge temperature sensorabnormalityContinue for 5 sec. — • Discharge temperature sensorH33 Indoor/Outdoor wrong connection — — • Indoor/Outdoor supply voltageH38 Indoor/Outdoor mismatch — — —H97 Outdoor Fan Motor lock abnormality 2 times occurrencewithin 30 minutes— • Outdoor PCB• Outdoor Fan MotorH98 Indoor high pressure protection — — • Air filter dirty• Air circulation short circuitH99 Indoor heat exchanger anti-freezingprotection— — • Insufficient refrigerant• Air filter dirtyF11 Cooling / Heating cycle changeoverabnormality4 times occurrencewithin 30 minutes— • 4-way valve• V-coilF90 PFC control 4 times occurrencewithin 10 minutes— • Voltage at PFCF91 Refrigeration cycle abnormality 2 times occurrencewithin 20 minutes— • No refrigerant(3-way valve is closed)F93 Outdoor compressor abnormal revolution 4 times occurrencewithin 20 minutes— • Outdoor compressorF95 Cool high pressure protection 4 times occurrencewithin 20 minutes— • Outdoor refrigerant circuitF96 IPM (power transistor) overheatingprotection— — • Excess refrigerant• Improper heat radiation• IPM (Power transistor)F97 Outdoor compressor overheatingprotection4 times occurrencewithin 20 minutes— • Insufficient refrigerant• CompressorF98 Total running current protection 3 times occurrencewithin 20 minutes— • Excess refrigerant• Improper heat radiationF99 Outdoor Direct Current (DC) peakdetection7 times occurrencecontinuously— • Outdoor PCB• IPM (Power transistor)• Compressor