8113.5. Indoor Fan Motor Operation13.5.1. Residual Heat Removal Control• To prevent high pressure at indoor unit, when heating mode thermostat-off condition or power supply OFF, indoor fan continue tooperate at controlled fan speed for maximum 30 seconds then stop.13.6. Powerful Mode Operation• When the power mode is selected, the internal setting temperature will shift lower up to 4°C for Cooling/Soft Dry or higher up to6°C for heating than remote control setting temperature, the powerful operation continue until user cancel the Powerful operationby pressing powerful button again.13.7. Auto restart control• When the power supply is cut off during the operation of air conditioner, the compressor will re-operate between three to fourminutes (10 patterns to be selected randomly) after power resume.• During multi split connection, Indoor unit will resume previous mode, include unit standby mode.13.8. Indication PanelNote:• If POWER LED is blinking (0.5 seconds ON, 0.5 second OFF), the possible operation of the unit are during Indoor Residual HeatRemoval, Hot Start, during Deice operation, operation mode judgment, or ON timer sampling.• If POWER LED is blinking (2.5 seconds ON, 0.5 second OFF), the unit is in standby mode.• If TIMER LED is blinking, there is an abnormality operation occurs.• If e-ion LED is blinking, there is an abnormality of e-ion occurs.• If PATROL LED is blinking, there is a gas sensor error detection.13.9. Mild Dry Cooling Operation• During multi split connection, Mild Dry Cooling Operation is disabled.LED POWER TIMER QUIET POWERFUL e-ion ECO PATROL PATROL SENSORColor Green Orange Orange Orange Blue Green BlueLight ON Operation ON Timer Setting ON Quiet Mode ON Powerful Mode ON e-ion ON Eco Patrol ON PATROL ONLight OFF Operation OFF Timer Setting OFF Quiet Mode OFF Powerful Mode OFF e-ion OFF Eco Patrol OFF PATROL OFF